background image

TR3EX

P. 6 / 7

EM-8632

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

Shows each module’s availability and error status.

0

15

Module 1
Module 2
Module 3
      :
Module 16

I/O DATA DESCRIPTIONS 

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

 

ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4, etc.)

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  Negative percentage is represented in 2’s 
complements.

0

15

 

TEMPERATURE DATA (models: R3-RS4, TS4 and US4, etc.)

16-bit binary data.
With °C  temperature unit, raw data is multiplied by 10.  For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.  For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

0

15

 

ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)

32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
32-bit data cannot be accessed using floating addresses.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

 

BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)

32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
32-bit data cannot be accessed using floating addresses.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

Summary of Contents for TR3EX

Page 1: ...use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration D...

Page 2: ...gh 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW...

Page 3: ...ground Caution This terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL COMM BUS Modbus TCP CONFIGURATION JACK JACK RJ 45 MODULAR JACK BUS CONNECTOR Not provided with No Power Supp...

Page 4: ...in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statisti...

Page 5: ...dules turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected Data Error Status indicates overrange R3 US4 out of 1...

Page 6: ...temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F...

Page 7: ...6659 8201 Fax 81 6 6659 8510 E mail info m system co jp DISCRETE DATA models R3 DA16 DC16 and RR8 etc 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF 1 ON Regarding d...

Reviews: