TR3EX

P. 2 / 7

EM-8632

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

COMPONENT IDENTIFICATION

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

ON

8

7

6

5

4

3

2

1

SW1

1

2

3

4

5

6

RUN LED

ERR LED

RJ-45 Modular 

Jack

Not used

Not used

Configuration 

Jack

Functions

LINK
DPLX (Duplex)
LINK10 (10Mbps)
LINK100

(100Mbps)
COL (Collision)

 FRONT VIEW

 SIDE VIEW

8

67

34

5

2

1

0

F

E

D

C

B

A

9

8

67

34

5

2

1

0

F

E

D

C

B

A

9

 

ETHERNET INDICATORS

ID

COLOR

FUNCTION

LINK

Red

ON at LINK

DPLX

Red

ON with full-duplex communication

LINK10

Red

ON with 10 Mbps connection

LINK100

Red

ON with 100 Mbps connection

COL

Red

Blinking when collision occurs

 

SIDE DIP SW

(*) Factory setting

• Data Allocation: SW1, SW2

Data Allocation Type* must be assigned to each I/O module 
position to specify how many data areas (four types) are to 
be occupied by each.
Two bits from SW1 and SW2 are assigned to each posi-
tion, and data areas can be specified from the module No. 1 
through 8.  Setting for No. 9 and later modules is identical 
to No. 8.

SW ASSIGNMENT

MODULE NO.

SW1-1

SW1-2

1

SW1-3

SW1-4

2

SW1-5

SW1-6

3

SW1-7

SW1-8

4

SW2-1

SW2-2

5

SW2-3

SW2-4

6

SW2-5

SW2-6

7

SW2-7

SW2-8

8

SW SETTTING

DATA ALLOCATION

OFF

OFF

1

ON

OFF

4

OFF

ON

8

ON

ON

16

* Refer to the specifications of the related series for the Data 

Allocation Type of I/O modules.

• Dual Communication: SW3-1

When two network modules are mounted, one must be  
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work.  For single communication, the network module must 
always be set to  ‘Main’ (OFF). 

SW

DUAL COMMUNICATION

MAIN (

*

)

SUB

SW3-1

OFF

ON

• Input Error Data: SW3-2
Hold:

 When the communication from an input module is lost 

due to the input module error, the network module holds the 
signal and stands by until the communication recovers.

Set to ‘0’:

 When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD

 

(

*

)

SET 

‘0’

SW3-2

OFF

ON

• LED Function: SW3-4

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED

RUN

ERR

OFF (*)

Green when normal

Green when abnormal

ON

Red when receiving

Red when transmitting

Note: Be sure to set unused SW3-3 to OFF

Summary of Contents for TR3EX

Page 1: ...use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration D...

Page 2: ...gh 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW...

Page 3: ...ground Caution This terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL COMM BUS Modbus TCP CONFIGURATION JACK JACK RJ 45 MODULAR JACK BUS CONNECTOR Not provided with No Power Supp...

Page 4: ...in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statisti...

Page 5: ...dules turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected Data Error Status indicates overrange R3 US4 out of 1...

Page 6: ...temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F...

Page 7: ...6659 8201 Fax 81 6 6659 8510 E mail info m system co jp DISCRETE DATA models R3 DA16 DC16 and RR8 etc 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF 1 ON Regarding d...

Reviews: