TR3EX

P. 1 / 7

EM-8632

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

ETHERNET INTERFACE MODULE

(Modbus/TCP, use with TR30)

MODEL

TR3EX

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

  Network interface module ............................................ (1)

 

MODEL NO.

Confirm that the model number described on the product is 
exactly what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

The equipment must be mounted inside the instrument 
panel of a metal enclosure.

• 

The actual installation environments such as panel con-
figurations, connected devices and connected wires may 
affect the protection level of this unit when it is integrat-
ed in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 

POWER INPUT RATINGS

• 

Operational range & power consumption: Check the pow-
er rating for the unit on the specification label.

  Rating 24V DC: 24V  ±10%, approx. 12W

 

UNPLUGGING THE MODULE

• 

Before you remove the module from its base or mount it, 
turn off the power supply for safety.

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -10 to +55°C     
(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

AND ....

• 

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base Model R3-BSx, or Model R3-
BSWx for free I/O address capability.

Before mounting the Network Interface Module onto the 
Base, be sure to configure the module as explained below.

 

DATA ALLOCATION

The setting determines the data area size assigned to each 
I/O module mounted on the base.
The data sent/received via Modbus is mapped according to 
this setting.
See “COMPONENT IDENTIFICATION.”

 

NODE ADDRESS

See “COMPONENT IDENTIFICATION.”

 

NETWORK SLOTS ON THE BASE

I/O 1

I/O 2

I/O n

With Model R3-BSx base, mount the I/O Modules from the 
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module is mounted basically at the right end 
though technically they could be mounted in any position.

With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each 
module using rotary switches equipped on the base.

Summary of Contents for TR3EX

Page 1: ...use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration D...

Page 2: ...gh 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW...

Page 3: ...ground Caution This terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL COMM BUS Modbus TCP CONFIGURATION JACK JACK RJ 45 MODULAR JACK BUS CONNECTOR Not provided with No Power Supp...

Page 4: ...in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statisti...

Page 5: ...dules turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected Data Error Status indicates overrange R3 US4 out of 1...

Page 6: ...temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F...

Page 7: ...6659 8201 Fax 81 6 6659 8510 E mail info m system co jp DISCRETE DATA models R3 DA16 DC16 and RR8 etc 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF 1 ON Regarding d...