TR3EX

P. 5 / 7

EM-8632

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

MODBUS I/O ASSIGNMENTS

ADDRESS

DATA TYPE

DATA

Coil (0X)

1 – 1024

Digital Output (discrete output)

Inputs (1X)

1 – 1024

Digital Input (discrete input)

1025 – 1040

Module Status

1041 – 1056

Error Status

1057 – 1072

Data Error Status

Input Registers (3X)

1 – 256

I

Analog Input

257 – 768

F

Analog Input

Holding Registers (4X)

1 – 256

I

Analog Output

257 – 768

F

Analog Output

I: Integer, 0 – 10000 (0 – 100%)
F: Floating (32-bit data cannot be accessed using floating addresses.)
Note: DO NOT access addresses other than mentioned above.  Such access may cause problems such as inadequate operation.

• 

Module Status indicates whether individual I/O module are mounted or not.  The bit corresponding to the mounted slots 
turns to “1”, and the unmounted slots to “0”.

• 

Error Status indicates error status for each module as described below.  The bit corresponding to such modules turns to “1”.

  R3-TSx, R3-RSx, R3-US4:  Input burnout

  R3-DA16A:   

 

Power input in error or disconnected

  R3-YSx:   

 

 

Output current error (e.g. load unconnected)

• 

Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each 
module.  The bit corresponding to such modules turns to “1”.

TRANSMISSION DATA ASSIGNMENTS

The DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     Module  1   

4

     Module  2   

4

     Module  3   

4

     Module  4   

1

     Module  5   

1

     Module  6   

1

     Module  7   

1

Then the I/O data are assigned as in the table below:

ADDRESS

POSITION

Input Registers (3X)
Holding Registers (4X)

1 – 4, 257 – 264

Slot 1

5 – 8, 265 – 272

Slot 2

9 – 12, 273 – 280

Slot 3

13, 281 – 282

Slot 4

14, 283 – 284

Slot 5

15, 285 – 286

Slot 6

16, 287 – 288

Slot 7

ADDRESS

POSITION

Coil (0X)
Inputs (1X)

1 – 64

Slot 1

65 – 128

Slot 2

129 – 192

Slot 3

193 – 208

Slot 4

209 – 224

Slot 5

225 – 240

Slot 6

241 – 256

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned 
data areas (Data Allocation Type) are allotted with the Data 
Allocation Type ‘1’ and ‘4’.  With ‘8’ and ‘16’, 64 (4 

×

 16) are 

automatically assigned.

Summary of Contents for TR3EX

Page 1: ...use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration D...

Page 2: ...gh 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW...

Page 3: ...ground Caution This terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL COMM BUS Modbus TCP CONFIGURATION JACK JACK RJ 45 MODULAR JACK BUS CONNECTOR Not provided with No Power Supp...

Page 4: ...in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statisti...

Page 5: ...dules turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected Data Error Status indicates overrange R3 US4 out of 1...

Page 6: ...temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F...

Page 7: ...6659 8201 Fax 81 6 6659 8510 E mail info m system co jp DISCRETE DATA models R3 DA16 DC16 and RR8 etc 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF 1 ON Regarding d...

Reviews: