![M-system SC100 Series User Manual Download Page 21](http://html1.mh-extra.com/html/m-system/sc100-series/sc100-series_user-manual_3126159021.webp)
21
SCCFG Users Manual EM-9192 Rev.4
ITEM
SUB ITEM
DATA
DEFAULT
CONTENTS
Language
Japanese, English
As specified
when ordering
Display language
Parameter setting
(40 parameters)
Setting
Enable, Disable
Disable
Enable / Disable the parameter in the User’s Pa-
rameter Table view.
Parameter
Max. 10 characters
Name
Parameter identification
GROUP
0 to 99
0
GROUP No. in the Function Block List
ITEM
0 to 99
0
ITEM No. in the Function Block List
Range Hi limit
*
3
±32000
10000
Engineering unit data’s upper range value
Range Lo limit
*
3
±32000
0
Engineering unit data’s lower range value
Decimal place
*
3
0 to 5
2
Engineering unit data’s decimal point position
DATA Hi limit
±32000
10000
DATA’s upper range value
DATA Lo limit
±32000
0
DATA’s lower range value
DATA decimal point
position
0 to 5
2
DATA’s decimal point position
DATA engineering unit Max. 8 characters
Unit
DATA’s engineering unit
*
1. Color chart
*
2. Storing interval and timing
INTERVAL
TIMING
INTERVAL
TIMING
1 sec.
Every sec.
1 min.
Every min. 0 sec.
2 sec.
Even number of sec.
2 min.
Even number of min. 0 sec.
5 sec.
0, 5, 10, ... 55 sec.
5 min.
0, 5, ... 55 min. 0 sec.
10 sec.
0, 10, 20 ... 50 sec.
10 min.
0, 10, ... 50 min. 0 sec.
20 sec.
0, 20, 40 sec.
30 min.
0, 30 min. 0 sec.
30 sec.
0, 30 sec.
60 min.
Every hour, 0 min. 0 sec.
*
3. LCD firmware version 1.5x or later