R9WTU-ED
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6225 Rev.1 P. 4 / 4
CONNECTING THE EXTENSION UNIT
1) Remove the cap.
2) Slide the two locks of the multi power monitoring unit to
the back position.
3) Connect the extension unit to the multi power monitor-
ing Unit.
4) Restore the two locks of the multi power monitoring unit
to the front position.
5) Mount the combined unit on a DIN rail.
Note: When you remove or mount the unit, turn off the power
supply and input signal for safety.
Lock
Cap
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.5 N·m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
6 (.24) max
3.3 (.13) max
mm (inch)