R3-PD16A
P. 7 / 10
EM-8397 Rev.1
■
ON/OFF CONTROL OUTPUT MODE
•
Data Length: 16 bits
Do 1 through 16 are assigned to Ch1 through 16.
When I/O Mode is in Output Operation (SW2-7: ON), Output Complete Status is not indicated.
Do
WRITE
ONE-SHOT OUTPUT/RESET
Di
OUTPUT COMPLETION STATUS
Do 1 Do 2
0 0
Not Operating
1 0
Ch1 Output
Di 1
Ch1 Output Completion Status
0 1
Ch2 Output
Di 2
Ch2 Output Completion Status
1 1
Output Data Reset
Do 3 Do 4
0 0
Not Operating
1 0
Ch3 Output
Di 3
Ch3 Output Completion Status
0 1
Ch4 Output
Di 4
Ch4 Output Completion Status
1 1
Output Data Reset
Do 5 Do 6
0 0
Not Operating
1 0
Ch5 Output
Di 5
Ch5 Output Completion Status
0 1
Ch6 Output
Di 6
Ch6 Output Completion Status
1 1
Output Data Reset
Do 7 Do 8
0 0
Not Operating
1 0
Ch7 Output
Di 7
Ch7 Output Completion Status
0 1
Ch8 Output
Di 8
Ch8 Output Completion Status
1 1
Output Data Reset
Do 9 Do 10
0 0
Not Operating
1 0
Ch9 Output
Di 9
Ch9 Output Completion Status
0 1
Ch10 Output
Di 10
Ch10 Output Completion Status
1 1
Output Data Reset
Do 11 Do 12
0 0
Not Operating
1 0
Ch11 Output
Di 11
Ch11 Output Completion Status
0 1
Ch12 Output
Di 12
Ch12 Output Completion Status
1 1
Output Data Reset
Do 13 Do 14
0 0
Not Operating
1 0
Ch13 Output
Di 13
Ch13 Output Completion Status
0 1
Ch14 Output
Di 14
Ch14 Output Completion Status
1 1
Output Data Reset
Do 15 Do 16
0 0
Not Operating
1 0
Ch15 Output
Di 15
Ch15 Output Completion Status
0 1
Ch16 Output
Di 16
Ch16 Output Completion Status
1 1
Output Data Reset
The above table shows the case of Not Swapped (SW2-8: OFF). ON/OFF control output is swapped with its pair when SW2-
8 is ON. The following is an example of Do1 and Do2.
Do
WRITE
ONE-SHOT OUTPUT/RESET
Di
OUTPUT COMPLETION STATUS
Do 1 Do 2
0 0
Not Operating
1 0
Ch2 Output
Di 2
Ch2 Output Completion Status
0 1
Ch1 Output
Di 1
Ch1 Output Completion Status
1 1
Output Data Reset