R3-PD16A
P. 2 / 10
EM-8397 Rev.1
COMPONENT IDENTIFICATION
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/ green) LED;
Green in normal operating conditions
Red with the abnormal configuration
Output status indicator
: Red LED; turns on with the
relays energized.
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
■
FRONT VIEW
■
SIDE VIEW
RUN LED
ERR LED
Status Indicator
LED
SW3
ON
4
3
2
1
Functions
Data Length
Output Mode
Output Hold
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
SW1
Output
ON Time
ON/OFF Control
Output Channel
Functions
ON
SW2
ON
I/O Mode
■
SIDE DIP SW
•
Output Hold:
SW3
Effective only in continuance output mode
SW
OUTPUT HOLD
HOLD
OFF
SW3-1
OFF (*)
ON
(*)Factory setting
•
Configuration:
SW3
SW
MODE
SW3-2
SW3-3
OFF
OFF
One-Shot Output Mode (*)
ON
OFF
ON/OFF Control Output Mode
OFF
ON
Continuance Output Mode
•
Data Length:
SW3
Effective only in ON/OFF control output mode
SW
DATA LENGTH
16 bit
8 bit
SW3-4
OFF (*)
ON
•
I/O Mode Setting:
SW2
Set output operation mode (Whether Output Complete
Status indicator is ON or OFF) *
1
SW
I/O OPERATION MODE
Input and Output
Output
SW2-7
OFF
(*)
ON
•
ON/OFF Control Output Channel:
SW2
ON/OFF control output channel is swappable with its pair.
SW
ON/OFF CONTROL OUTPUT CHANNEL
Not Swapped
Swapped
SW2-8
OFF
(*)
ON
*1. Output completion status is compatible with interface
modules model: R3-NC1, -NC3, -NE1, -NM1 and -NDx of
firmware version V2.00 or higher. Other interface modules
are not compatible. So, set I/O Mode as output (SW2-7: ON)
to use it.
Note: R3-NL1 and R3-NL2 are not available with this mod
-
el.