16 samples and 32 samples, and press Set button.

3) Press Mode button to save the setting and exit the Mov-

ing Average setting.

HYSTERESIS (DEADBAND)

1) Choose Hysteresis from the Set Up Transmitter and 

press Set button.

2) Use Up-Down buttons to choose L1 deadband within the 

display scale range and press Set button.

3) Use Up-Down buttons to choose L2 through L4 in the 

same manner.  Pressing Set button shifts the cursor posi-

tion to a next point.

4) Press Mode button to save the setting and exit the Hys-

teresis setting.

ALARM LATCHING

An alarm with latching option does not automatically reset 
once the alarm is tripped, until the setting is enabled, or the 
power supply is turned off and on.

1) Choose Latching from the Set Up Transmitter and press 

Set button.

2) Use Up-Down buttons to choose Enable or Disable and 

press Set button.

3) Press Mode button to save the setting and exit the Alarm 

Latching setting.

 

LCD SETTING MODE

Press Mode button for at least 2 seconds to show the Con-
tents and choose LCD Mode, and press Set button.
Once in the LCD Mode, you can move from one parameter to 
another by pressing Mode button briefly.
When all the setting is complete, press the Mode button for 
at least 2 seconds to return to the Monitor Mode.

DISPLAY CONTRAST

1) Choose Contrast from the LCD Mode and press Set but-

ton.

2) Use Up-Down buttons to choose an appropriate contrast 

in %.  Alternatively, press Set button to set the contrast 

to 50%.

3) Press Mode button to save the setting and exit the Con-

trast setting.

DISPLAY BACKLIGHT

1) Choose Back Light from the LCD Mode and press Set 

button.

2) Use Up-Down buttons to choose either On, Off, or Off 

Timer and press Set button.

3) If Off Timer is selected, specify also a time before the 

backlight is off from 1 to 3600 seconds.

4) Press Mode button to save the setting and exit the Back 

Light setting.

Whatever is this setting, a red backlight is maintained 
while the unit is in alarm conditions.

 

INFORMATION MODE

Press Mode button for at least 2 seconds to show the Con-
tents and choose Information, and press Set button.
Once in the Information, you can move from one parameter 
to another by pressing Mode button briefly.
When all the setting is complete, press the Mode button for 
at least 2 seconds to return to the Monitor Mode.

PROPERTY

This menu is for display purpose only.

1) Choose Property from the Information and press Set but-

ton.

2) Model, Firmware version, Serial and Tag numbers are 

shown.

3) Press Mode button to exit the Property.

TAG NUMBER (NAME)

1) Choose Tag No. from the Information and press Set but-

ton.

2) Use Up-Down buttons to choose a first character and 

press Set button to confirm and shift the cursor to a next 

position.  A second character can be entered in the same 

manner, up to 10 characters.

3) Press Mode button to save the setting and exit the Tag 

No. setting.

 

ALARM TEST MODE

The output relays can be manually turned on and off with-
out applying input signals for testing purposes.  While in 
this mode, the actual input signal does not affect the output 
relay operation.

1) Press Mode button for at least 2 seconds to show the Con-

tents and choose Alarm Test, and press Set button.

2) Press Set button one or more times to shift the cursor 

position to the alarm point for which you want to conduct 

testing.

3) Use Up-Down buttons to switch the relay on and off.
4) Press Set button to go to other alarm points and test in 

the same manner.

5) Press the Mode button for at least 2 seconds to return to 

the Monitor Mode.

Summary of Contents for M7EASDY

Page 1: ...nts Failure to observe these re quirements may invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE...

Page 2: ... one Use a minus screwdriver to tighten the screw DIN Rail 35mm wide Spring Loaded DIN Rail Adaptor DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to EXTE...

Page 3: ... COM N C N O COM 10 11 6 9 3 7 8 5 L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM 6 9 3 7 8 5 L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM Output Code 5 SPDT Relay Output Code 2 N O Relay Output Code 3 N C Relay CONFIGURATOR JACK CONFIGURATOR JACK 4 1 2 2 WIRE TRANSMITTER V 1 5V DC MONITOR 4 1 2 2 WIRE TRANSMITTER V 1 5V DC MONITOR When 24V DC is Not Used U V POWER U V POWER 50Ω 200Ω No Connec...

Page 4: ...Input Value Down Used to switch the output display informa tion when the input display information is set to Scaled Range Value Coil Trip Action Alarm Setpoints In Coil Trip Action mode symbols mean the following E Energize D De energize High alarm trip Lo alarm trip PARAMETER LOCK The M7EASDY starts operating in the Monitor Mode with the Parameter Lock when the power supply is turned on In order ...

Page 5: ... 4 Use Up Down buttons to choose an X value 7 5 to 107 5 and press Set button 5 Use Up Down buttons to choose a corresponding Y value from 9999 to 9999 and press Set button 6 Press Mode button to save the setting and exit the Lin earizer setting ALARM SETTING Alarm Setpoints 1 Choose Alarm from the Set Up Transmitter and press Set button 2 Choose Setting Value and press Set button 3 Use Up Down bu...

Page 6: ...ode and press Set button 2 Use Up Down buttons to choose either On Off or Off Timer and press Set button 3 If Off Timer is selected specify also a time before the backlight is off from 1 to 3600 seconds 4 Press Mode button to save the setting and exit the Back Light setting Whatever is this setting a red backlight is maintained while the unit is in alarm conditions INFORMATION MODE Press Mode butt...

Page 7: ...oint Select 0 9999 1 999 9 2 99 99 3 9 999 Set 0 Set 100 Set in 0 00 to 99 99 Set 0 Set 100 0 20mA Zero 99 99 to 99 99 Span 0 000 to 9 999 Set 0 Set 100 Selectable from 9999 to 9999 Enter input value in scaled range Unit Scale unit Select L1 L2 L3 L4 Hi or Lo alarm trip Energize or De energize Select L1 L2 L3 L4 Set 0 Set 100 Selectable from 9999 to 9999 Linearization Table X Input Y Linearized va...

Page 8: ... L3 L4 Select Disable Enable Setting 0 to 100 Select On Off Off Timer Off Time Setting xxxx sec Back Light Contrast LCD Mode Property Latching Hysteresis deadband Moving Average Alarm ON Delay Timer Power ON Delay Timer Display Selectable from 0 to 99 Selectable from 0 to 999 Selectable from 0 to 3600 Enter input value in scale MODEL Complete model number FIRMWARE Version No SER NO Serial number T...

Page 9: ...he maxi mum For maximum relay life with inductive load exter nal protection is recommended 0 50 100 Input LL L HH H L2 5 7 L3 5 8 L4 3 9 L1 3 6 ON ON OFF ON ON OFF OFF OFF Example Quad N O contacts LL L H HH Alarm Trip Operation Terminal No in parentheses Trip operation in power failure Output code 2 All relays turn OFF Output code 3 All relays turn ON Output code 5 Terminals 3 9 5 8 turn ON MAINT...

Reviews: