EM-7763  Rev.5  P. 9 / 9

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

full-scale.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output load is 250 V AC / 

120 VA or 125 V DC / 30 W  (250 V AC / 480 VA or 125 V 

DC / 150 W for dual alarm, Output Code 5) at the maxi-

mum.  For maximum relay life with inductive load, exter-

nal protection is recommended.

0

50

100

Input

%

LL

L

HH

H

L2 (5–7)

L3 (5–8)

L4 (3–9)

L1 (3–6)

ON

ON

OFF

ON

ON

OFF

OFF

OFF

• Example   

Quad N.O. contacts (LL, L, H, HH)

Alarm Trip Operation  

Terminal No. in parentheses

Trip operation in power failure
   Output code 2

: All relays turn OFF.

   

Output code 3

: All relays turn ON.

   

Output code 5

: Terminals 3 – 9, 5 – 8 turn ON.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• H (HH) Setpoint

   Increase the input signal from a value lower than the set-

point and check that the relay trips at the H (or HH) set-
point within the setpoint accuracy described in the data 
sheet.

• L (LL) Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the relay trips at the L (or LL) 
setpoint within the setpoint accuracy described in the 
data sheet.

When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for M7EASDY

Page 1: ...nts Failure to observe these re quirements may invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE...

Page 2: ... one Use a minus screwdriver to tighten the screw DIN Rail 35mm wide Spring Loaded DIN Rail Adaptor DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to EXTE...

Page 3: ... COM N C N O COM 10 11 6 9 3 7 8 5 L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM 6 9 3 7 8 5 L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM Output Code 5 SPDT Relay Output Code 2 N O Relay Output Code 3 N C Relay CONFIGURATOR JACK CONFIGURATOR JACK 4 1 2 2 WIRE TRANSMITTER V 1 5V DC MONITOR 4 1 2 2 WIRE TRANSMITTER V 1 5V DC MONITOR When 24V DC is Not Used U V POWER U V POWER 50Ω 200Ω No Connec...

Page 4: ...Input Value Down Used to switch the output display informa tion when the input display information is set to Scaled Range Value Coil Trip Action Alarm Setpoints In Coil Trip Action mode symbols mean the following E Energize D De energize High alarm trip Lo alarm trip PARAMETER LOCK The M7EASDY starts operating in the Monitor Mode with the Parameter Lock when the power supply is turned on In order ...

Page 5: ... 4 Use Up Down buttons to choose an X value 7 5 to 107 5 and press Set button 5 Use Up Down buttons to choose a corresponding Y value from 9999 to 9999 and press Set button 6 Press Mode button to save the setting and exit the Lin earizer setting ALARM SETTING Alarm Setpoints 1 Choose Alarm from the Set Up Transmitter and press Set button 2 Choose Setting Value and press Set button 3 Use Up Down bu...

Page 6: ...ode and press Set button 2 Use Up Down buttons to choose either On Off or Off Timer and press Set button 3 If Off Timer is selected specify also a time before the backlight is off from 1 to 3600 seconds 4 Press Mode button to save the setting and exit the Back Light setting Whatever is this setting a red backlight is maintained while the unit is in alarm conditions INFORMATION MODE Press Mode butt...

Page 7: ...oint Select 0 9999 1 999 9 2 99 99 3 9 999 Set 0 Set 100 Set in 0 00 to 99 99 Set 0 Set 100 0 20mA Zero 99 99 to 99 99 Span 0 000 to 9 999 Set 0 Set 100 Selectable from 9999 to 9999 Enter input value in scaled range Unit Scale unit Select L1 L2 L3 L4 Hi or Lo alarm trip Energize or De energize Select L1 L2 L3 L4 Set 0 Set 100 Selectable from 9999 to 9999 Linearization Table X Input Y Linearized va...

Page 8: ... L3 L4 Select Disable Enable Setting 0 to 100 Select On Off Off Timer Off Time Setting xxxx sec Back Light Contrast LCD Mode Property Latching Hysteresis deadband Moving Average Alarm ON Delay Timer Power ON Delay Timer Display Selectable from 0 to 99 Selectable from 0 to 999 Selectable from 0 to 3600 Enter input value in scale MODEL Complete model number FIRMWARE Version No SER NO Serial number T...

Page 9: ...he maxi mum For maximum relay life with inductive load exter nal protection is recommended 0 50 100 Input LL L HH H L2 5 7 L3 5 8 L4 3 9 L1 3 6 ON ON OFF ON ON OFF OFF OFF Example Quad N O contacts LL L H HH Alarm Trip Operation Terminal No in parentheses Trip operation in power failure Output code 2 All relays turn OFF Output code 3 All relays turn ON Output code 5 Terminals 3 9 5 8 turn ON MAINT...