bration setting.

• Low Cut

1) Choose Input from the Set Up Transmitter and press Set 

button.

2) Choose Low Cut and press Set button.
3) Use Up-Down buttons to choose the low-end cutout value 

(0.00 to 99.99%) and press Set button.

4) Press Mode button to save the setting and exit the Low 

Cut setting.

• Scaling (Engineering Unit & Decimal Point Position)

1) Choose Input from the Set Up Transmitter and press Set 

button.

2) Choose Scaling and press Set button.
3) Engineering Unit
  Choose Unit and press Set button.
4) Use Up-Down buttons to choose an unit from the selec-

tions (A, mA, V, mV, W, mW, %, °C, °F, Pa, kPa, MPa, User 

Unit) and press Set button.

5) If User Unit is selected, an user-specific unit can be com-

posed on the display. Use Up-Down buttons to choose a 

first character and press Set button to confirm and shift 

the cursor to a next position. A second character can be 

entered in the same manner, up to 10 characters.

6) Press Mode button to save the setting and exit the User 

Unit setting.

7) Decimal Point Position
  Choose Decimal Point and press Set button.
8) Use Up-Down buttons to choose an appropriate position 

from the following selections:

   

0: 9999 

1: 999.9

   

2: 99.99 

3: 9.999

  The decimal point is applied only to the display value.
9) Press Mode button to save the setting and exit the Deci-

mal Point setting.

• Scaling (Linearizer)

1) Linearizer
  Choose Linearizer and press Set button.
2) Use Up-Down buttons to choose a function among: Linear 

(proportional), Sqrt (square root extraction) and User Ta-

ble (segment linearization).

 

Linear or Sqrt

  Specify 0% and 100% input values in engineering unit.
3) Use Up-Down buttons to choose 0% display value from 

-9999 to +9999 and press Set button.

4) Use Up-Down buttons to choose 100% display value from 

-9999 to +9999 and press Set button (Set to scaling 0% < 

scaling 100%).

5) Press Mode button to save the setting and exit the Lin-

earizer setting.

 

User Table

  Specify pairs of input % X and output values in engineer-

ing unit Y.  Max. 128 points (pairs) are selectable (0 to 127) 

Reverse setting is available.

3) Use Up-Down buttons to choose a calibration point and 

press SET.

4) Use Up-Down buttons to choose an X value (-7.5 to 

+107.5%) and press Set button.

5) Use Up-Down buttons to choose a corresponding Y value 

from -9999 to +9999 and press Set button.

6) Press Mode button to save the setting and exit the Lin-

earizer setting.

ALARM SETTING

• Alarm Setpoints

1) Choose Alarm from the Set Up Transmitter and press Set 

button.

2) Choose Setting Value and press Set button.
3) Use Up-Down buttons to choose L1 setpoint within the 

display scale range and press Set button.  Display unit is 

indicated on the screen.

4) Use Up-Down buttons to choose L2 through L4 in the 

same manner.  Pressing Set button shifts the cursor posi-

tion to a next point.

5) Press Mode button to save the setting and exit the Set-

ting Value setting.

• Alarm Trip Actions

1) Choose Alarm from the Set Up Transmitter and press Set 

button.

2) Choose Trip Operation and press Set button.
3) Use Up-Down buttons to choose Hi (High alarm trip) or 

Lo (Low alarm trip) for the L1 setpoint and press Set but-

ton.

4) Use Up-Down buttons to choose trip actions for the L2 

through L4 in the same manner.  Pressing Set button 

shifts the cursor position to a next point.

5) Press Mode button to save the setting and exit the Trip 

Operation setting.

• Coil Energized or De-energized at Alarm

1) Choose Alarm from the Set Up Transmitter and press Set 

button.

2) Choose Coil at Alarm and press Set button.
3) Use Up-Down buttons to choose Energize or De-energize 

for the L1 setpoint and press Set button.

4) Use Up-Down buttons to choose coil type for the L2 

through L4 in the same manner.  Pressing Set button 

shifts the cursor position to a next point.

5) Press Mode button to save the setting and exit the Coil at 

Alarm setting.

POWER ON DELAY TIMER

1) Choose Power ON Delay Timer from the Set Up Trans-

mitter and press Set button.

2) Use Up-Down buttons to choose a delay time from 0 to 99 

seconds and press Set button.

3) Press Mode button to save the setting and exit the Power 

ON Delay Timer setting.

ALARM ON DELAY TIMER

1) Choose Alarm ON Delay Timer from the Set Up Trans-

mitter and press Set button.

2) Use Up-Down buttons to choose a delay time from 0 to 

999 seconds and press Set button.

3) Press Mode button to save the setting and exit the Alarm 

ON Delay Timer setting.

MOVING AVERAGE

1) Choose Moving Average from the Set Up Transmitter 

and press Set button.

2) Use Up-Down buttons to choose a number of samples 

from None (No average function), 4 samples, 8 samples, 

Summary of Contents for M7EASDY

Page 1: ...nts Failure to observe these re quirements may invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE...

Page 2: ... one Use a minus screwdriver to tighten the screw DIN Rail 35mm wide Spring Loaded DIN Rail Adaptor DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to EXTE...

Page 3: ... COM N C N O COM 10 11 6 9 3 7 8 5 L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM 6 9 3 7 8 5 L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM Output Code 5 SPDT Relay Output Code 2 N O Relay Output Code 3 N C Relay CONFIGURATOR JACK CONFIGURATOR JACK 4 1 2 2 WIRE TRANSMITTER V 1 5V DC MONITOR 4 1 2 2 WIRE TRANSMITTER V 1 5V DC MONITOR When 24V DC is Not Used U V POWER U V POWER 50Ω 200Ω No Connec...

Page 4: ...Input Value Down Used to switch the output display informa tion when the input display information is set to Scaled Range Value Coil Trip Action Alarm Setpoints In Coil Trip Action mode symbols mean the following E Energize D De energize High alarm trip Lo alarm trip PARAMETER LOCK The M7EASDY starts operating in the Monitor Mode with the Parameter Lock when the power supply is turned on In order ...

Page 5: ... 4 Use Up Down buttons to choose an X value 7 5 to 107 5 and press Set button 5 Use Up Down buttons to choose a corresponding Y value from 9999 to 9999 and press Set button 6 Press Mode button to save the setting and exit the Lin earizer setting ALARM SETTING Alarm Setpoints 1 Choose Alarm from the Set Up Transmitter and press Set button 2 Choose Setting Value and press Set button 3 Use Up Down bu...

Page 6: ...ode and press Set button 2 Use Up Down buttons to choose either On Off or Off Timer and press Set button 3 If Off Timer is selected specify also a time before the backlight is off from 1 to 3600 seconds 4 Press Mode button to save the setting and exit the Back Light setting Whatever is this setting a red backlight is maintained while the unit is in alarm conditions INFORMATION MODE Press Mode butt...

Page 7: ...oint Select 0 9999 1 999 9 2 99 99 3 9 999 Set 0 Set 100 Set in 0 00 to 99 99 Set 0 Set 100 0 20mA Zero 99 99 to 99 99 Span 0 000 to 9 999 Set 0 Set 100 Selectable from 9999 to 9999 Enter input value in scaled range Unit Scale unit Select L1 L2 L3 L4 Hi or Lo alarm trip Energize or De energize Select L1 L2 L3 L4 Set 0 Set 100 Selectable from 9999 to 9999 Linearization Table X Input Y Linearized va...

Page 8: ... L3 L4 Select Disable Enable Setting 0 to 100 Select On Off Off Timer Off Time Setting xxxx sec Back Light Contrast LCD Mode Property Latching Hysteresis deadband Moving Average Alarm ON Delay Timer Power ON Delay Timer Display Selectable from 0 to 99 Selectable from 0 to 999 Selectable from 0 to 3600 Enter input value in scale MODEL Complete model number FIRMWARE Version No SER NO Serial number T...

Page 9: ...he maxi mum For maximum relay life with inductive load exter nal protection is recommended 0 50 100 Input LL L HH H L2 5 7 L3 5 8 L4 3 9 L1 3 6 ON ON OFF ON ON OFF OFF OFF Example Quad N O contacts LL L H HH Alarm Trip Operation Terminal No in parentheses Trip operation in power failure Output code 2 All relays turn OFF Output code 3 All relays turn ON Output code 5 Terminals 3 9 5 8 turn ON MAINT...

Reviews: