MOVING AVERAGE SAMPLE NUMBER

1) Hold down [M] for 3 seconds* and push [M] to choose [P].
2) Press [UP] and [DOWN] buttons at once.  Current setting 

value is shown at the right end of the digital indicator, 

with ‘A.’ at the left end.

  Factory default setting is “4”.
3) Press [UP] or [DOWN] buttons until the indicator shows 

the desired value (1, 2, 4, 8 or 16), and press [SET].

 

LED BRIGHTNESS ADJUSTMENT

1) Hold down [M] for 3 seconds* and push [M] to choose [P].
2) Press [UP] and [DOWN] buttons at once for two times.  

Current setting value is shown on the digital indicator, 

with ‘c.’ at the left end.  Factory default setting is ‘7,’ the 

brightest.

3) Press [UP] or [DOWN] buttons until the indicator shows 

the desired setting (1 through 7), and press [SET].

*  The [M] button remain activated for 1 minute after it has 

been used to choose a indicator LED (programming mode).  
During this period, pressing the [M] button briefly is enough 
to choose another indicator.  After 1 minute, it turns to deac-
tivated state.

CALIBRATION PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the indication to a receiving instrument or in 
case of regular calibration, adjust the output as explained 
in the following.

 

HOW TO CALIBRATE THE OUTPUT INDICATION

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust the bargraph and  

digital indicator to 0% following the each procedure ex-

plained in “ADJUSTMENT PROCEDURE.”

2) SPAN:  Apply 100% input and adjust the bargraph and 

digital indicator to 100% following the same procedure.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular checking procedure is explained below:

 

CHECKING

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the bargraph 
and digital indicator for the respective input signal remains 
within accuracy described in the data sheet.  When the bar-
graph and digital indicator are out of tolerance, recalibrate 
the unit according to the “CALIBRATION PROCEDURE” 
explained earlier.

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protectors for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for 48NDV

Page 1: ...system The user may have to review the CE or UKCA requirements in regard to the whole system and employ additional protective measures to ensure the CE or UKCA conformity In order to enable the operator to turn off the power in put immediately install a switch or a circuit breaker ac cording to the relevant requirements in IEC 60947 2 and properly indicate it POWER INPUT RATING OPERATIONAL RANGE L...

Page 2: ...STERED MOUNTING Not conform to degree of protection IP65 1 0 61 5 min USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel cutout size is as specified in the unit s data sheet 31 5 138 mm Three types of bezels are selectable when ordering Standard type Fits into M System s 48 Series panel cutout 38 139 5 mm Option D type Fits...

Page 3: ...nd below the unit for ventilation Bracket TERMINAL CONNECTIONS Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit EXTERNAL DIMENSIONS unit mm inch 75 2 95 103 4 06 10 39 18 71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16 M3 SCREW TERMINALS 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 31 1 22 100 3 94 Rounded corners for the option D OPTION D BEZEL 3 ...

Page 4: ...c PAJ PAK PBA 44 138 mm etc STANDARD BEZEL 2 10 4 41 7 5 30 3 9 15 136 5 5 37 144 5 67 11 4 45 7 5 30 4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 CONNECTION DIAGRAM ALARM OUTPUT CODE 4 4 points ALARM OUTPUT CODE 2 2 points ALARM OUTPUT CODE 0 None 1 2 12 13 14 INPUT 15 16 1 2 12 13 14 15 16 INPUT LLa 11 La LLb Lc LLc 7 8 9 8 9 10 HHa 7 Hc HHc HHb Ha HH OUT...

Page 5: ...Settings Mode Setting Selector Setting DOWN Button Switcing Detailed Settings Digital Indicator Setpoint 2 Value Setpoint 1 Value PV Indicator Note Setpoint 1 or 2 provided only for the multi color bar type ALARM OUTPUT CODE 0 None SET ENTER Button H Setpoint Adj Alarm Function Span Adj Setting Decimal Point Position Moving Average Brightness Adj Zero Adj Setting L Setpoint Adj Alarm Function Sett...

Page 6: ...Delay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjustment Digital Indicator Bargraph Z SET Z M Increase Decrease Zero Adjustment Digital Indicator Only Complete Z ON LED OFF SPAN ADJUSTMENT Apply 100 input signal before adjustment All alarm setpoints ...

Page 7: ...itched to continuous ON state 4 Press UP or DOWN buttons until the bargraph shows 100 and the digital indicator comes to a desired value and press SET DIGITAL INDICATOR SPAN ADJUSTMENT 1 Hold down M for 3 seconds and push M to choose S 2 Press UP or DOWN buttons until the digital indicator comes to a desired value and press SET DECIMAL POINT POSITION 1 Hold down M for 3 seconds and push M to choos...

Page 8: ...ibration adjust the output as explained in the following HOW TO CALIBRATE THE OUTPUT INDICATION Use a signal source and measuring instruments of sufficient accuracy level Turn the power supply on and warm up for more than 10 minutes 1 ZERO Apply 0 input and adjust the bargraph and digital indicator to 0 following the each procedure ex plained in ADJUSTMENT PROCEDURE 2 SPAN Apply 100 input and adju...

Reviews: