LED OFF

LED Blinking

Mode Selector

*

1

UP / DOWN Button

 

MOVING AVERAGE SAMPLE NUMBERS

P

M

Press at once

Moving Average

Sample Numbers

Increase / Decrease

Complete

Digital Indicator

SET

P

LED OFF

LED Blinking

Mode Selector

*

1

UP / DOWN Button

 

LED BRIGHTNESS ADJUSTMENT

P

M

Press at once

LED Brightness Adjustment

Increase / Decrease

*

2

Complete

Digital Indicator

SET

P

Digital Indicator

Press at once

*

1. Keep pressing at least for 3 seconds to activate Mode Selector M.  Press briefly for second and more times within 1 minute after it has been activated.

*

2. Pressing UP or DOWN button shifts the LED brightness in 7 levels.  Factory default is set to 7, the brightest level.

Note: Each setting sequence is complete only when SET button is pressed.  Once set, parameters are not lost even after the power is removed.

 

BARGRAPH / DIGITAL INDICATOR ZERO ADJUSTMENT

1) Apply 0% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [Z].
3) Press [UP] and [DOWN] buttons at once. (Blinking Z 

LED is switched to continuous ON state.)

4) Press [UP] or [DOWN] buttons until the bargraph shows 

0%, and the digital indicator comes to a desired value, 

and press [SET].  

 

DIGITAL INDICATOR ZERO ADJUSTMENT

1) Hold down [M] for 3 seconds* and push [M] to choose [Z].
2) Press [UP] or [DOWN] buttons until the digital indicator 

comes to a desired value, and press [SET].  

 

BARGRAPH / DIGITAL INDICATOR SPAN ADJUSTMENT

1) Apply 100% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [S].
3) Press [UP] and [DOWN] buttons at once. (Blinking S 

LED is switched to continuous ON state.)

4) Press [UP] or [DOWN] buttons until the bargraph shows 

100%, and the digital indicator comes to a desired value, 

and press [SET].  

 

DIGITAL INDICATOR SPAN ADJUSTMENT

1) Hold down [M] for 3 seconds* and push [M] to choose [S].
2) Press [UP] or [DOWN] buttons until the digital indicator 

comes to a desired value, and press [SET].  

 

DECIMAL POINT POSITION

1) Hold down [M] for 3 seconds* and push [M] to choose [P].
2) Press [UP] or [DOWN] buttons until the decimal point 

comes to a desired position, and press [SET].

 

ALARM SETPOINT ADJUSTMENTS

• 48NDV-2:  H 

[L setpoint] to 100%

 

 

   L 0% 

to 

[H 

setpoint]

     

 

 

No alarm trip is selectable

• 48NDV-4:  HH  [H setpoint] to 100%

     

 

 

[L setpoint] to [HH setpoint]

     

 

 

[LL setpoint] to [H setpoint]

     

 

 

LL  0% to [L setpoint]

     

 

 

No alarm trip is selectable

• How to Set LL (or L, H, HH, 1, 2) Setpoints

1) Hold down [M] for 3 seconds* and push [M] to choose 

[LL].

2) Press [UP] or [DOWN] buttons until the indicator comes 

to the desired position, and press [SET].  

  (Same procedure for L, H, HH, 1, 2 setpoints)

• How to Cancel HH and H Alarms

1) Press [UP] or [DOWN] buttons until the indicator comes 

to the upper limit (digital indicator shows “----”), and 

press [SET].  

  HH indicator must be set before H as the H setpoint can-

not go above the HH setpoint.

• How to Cancel LL and L Alarms

1) Press [UP] or [DOWN] buttons until the indicator comes 

to the lower limit (digital indicator shows “----”), and 

press [SET].  

  LL indicator must be set before L as the L setpoint can-

not go below the LL setpoint.

 

LL (or L, H, HH) ALARM ON TIME DELAY

1) Hold down [M] for 3 seconds* and push [M] to choose 

[LL].

2) Press [UP] and [DOWN] buttons at once.  Current setting 

value in seconds is shown at the right end of the digital 

indicator, with ‘d.’ at the left end.

  Factory default setting is “0”.
3) Press [UP] or [DOWN] buttons until the meter shows the 

desired value, and press [SET]. (The range between 0 to 

15 sec. can be set.)

  (Same procedure for L, H, HH, 1, 2 setpoints)

Summary of Contents for 48NDV

Page 1: ...system The user may have to review the CE or UKCA requirements in regard to the whole system and employ additional protective measures to ensure the CE or UKCA conformity In order to enable the operator to turn off the power in put immediately install a switch or a circuit breaker ac cording to the relevant requirements in IEC 60947 2 and properly indicate it POWER INPUT RATING OPERATIONAL RANGE L...

Page 2: ...STERED MOUNTING Not conform to degree of protection IP65 1 0 61 5 min USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel cutout size is as specified in the unit s data sheet 31 5 138 mm Three types of bezels are selectable when ordering Standard type Fits into M System s 48 Series panel cutout 38 139 5 mm Option D type Fits...

Page 3: ...nd below the unit for ventilation Bracket TERMINAL CONNECTIONS Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit EXTERNAL DIMENSIONS unit mm inch 75 2 95 103 4 06 10 39 18 71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16 M3 SCREW TERMINALS 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 31 1 22 100 3 94 Rounded corners for the option D OPTION D BEZEL 3 ...

Page 4: ...c PAJ PAK PBA 44 138 mm etc STANDARD BEZEL 2 10 4 41 7 5 30 3 9 15 136 5 5 37 144 5 67 11 4 45 7 5 30 4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 CONNECTION DIAGRAM ALARM OUTPUT CODE 4 4 points ALARM OUTPUT CODE 2 2 points ALARM OUTPUT CODE 0 None 1 2 12 13 14 INPUT 15 16 1 2 12 13 14 15 16 INPUT LLa 11 La LLb Lc LLc 7 8 9 8 9 10 HHa 7 Hc HHc HHb Ha HH OUT...

Page 5: ...Settings Mode Setting Selector Setting DOWN Button Switcing Detailed Settings Digital Indicator Setpoint 2 Value Setpoint 1 Value PV Indicator Note Setpoint 1 or 2 provided only for the multi color bar type ALARM OUTPUT CODE 0 None SET ENTER Button H Setpoint Adj Alarm Function Span Adj Setting Decimal Point Position Moving Average Brightness Adj Zero Adj Setting L Setpoint Adj Alarm Function Sett...

Page 6: ...Delay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjustment Digital Indicator Bargraph Z SET Z M Increase Decrease Zero Adjustment Digital Indicator Only Complete Z ON LED OFF SPAN ADJUSTMENT Apply 100 input signal before adjustment All alarm setpoints ...

Page 7: ...itched to continuous ON state 4 Press UP or DOWN buttons until the bargraph shows 100 and the digital indicator comes to a desired value and press SET DIGITAL INDICATOR SPAN ADJUSTMENT 1 Hold down M for 3 seconds and push M to choose S 2 Press UP or DOWN buttons until the digital indicator comes to a desired value and press SET DECIMAL POINT POSITION 1 Hold down M for 3 seconds and push M to choos...

Page 8: ...ibration adjust the output as explained in the following HOW TO CALIBRATE THE OUTPUT INDICATION Use a signal source and measuring instruments of sufficient accuracy level Turn the power supply on and warm up for more than 10 minutes 1 ZERO Apply 0 input and adjust the bargraph and digital indicator to 0 following the each procedure ex plained in ADJUSTMENT PROCEDURE 2 SPAN Apply 100 input and adju...

Reviews: