EM-9436-A  Rev.12  P. 6 / 8

ADJUSTMENT PROCEDURE

L

SET

L

M

Increase / Decrease

L Setpoint

Complete

LL

SET

LL

M

Increase / Decrease

LL Setpoint

Complete

H

M

Press at once

ON Time Delay for 

H Setpoint

Increase / Decrease

Complete

Digital Indicator

H

SET

H

M

Increase / Decrease

H Setpoint

Complete

HH

SET

HH

M

Increase / Decrease

HH Setpont

Complete

2

SET

2

M

Increase / Decrease

Increase / Decrease

Setpoint 2

Complete

1

SET

1

M

Setpoint 1

Complete

LED OFF

LED OFF

LED Blinking

Mode Selector

*

1

UP / DOWN Button

UP / DOWN Button

LED Blinking

Mode Selector

*

1

UP / DOWN Button

LED Blinking

Mode Selector

*

1

UP / DOWN Button

LED Blinking

Mode Selector

*

1

 

ZERO ADJUSTMENT

: Apply 0% input signal before adjustment.  All alarm setpoints will be reset after the adjustment.

SET

H

HH

M

Press at once

ON Time Delay for 

HH Setpoint

Increase / Decrease

Complete

Digital Indicator

SET

HH

 L

M

Press at once

ON Time Delay for 

L Setpoint

Increase / Decrease

Complete

Digital Indicator

SET

L

LL

M

Press at once

ON Time Delay for

LL Setpoint

Increase / Decrease

Complete

Digital Indicator

SET

LL

Z

M

Press at once

Zero Adjustment

Digital Indicator / Bargraph

Z

SET

Z

M

Increase / Decrease

Zero Adjustment

Digital Indicator Only

Complete

Z

ON

LED OFF

 

SPAN ADJUSTMENT

: Apply 100% input signal before adjustment.  All alarm setpoints will be reset after the adjustment.

S

LED OFF

 

DECIMAL POINT POSITION

 

ALARM SETTING

: Proceed after the zero / span adjustments and the decimal point position setting.

• 48NDV-4, 48NDV-2

 

*

2

• 48NDV-0

 

*

3

*

1. Keep pressing at least for 3 seconds to activate Mode Selector M.  Press briefly for second and more times within 1 minute after it has been activated.

*

2. HH or LL setpoints are not provided for the 48NDV-2.

*

3. 1 or 2 setpoints are not provided for the 48NDV-0R, -0Y, -0G or -0B.

Note: Each setting sequence is complete only when SET button is pressed.  Once set, parameters are not lost even after the power is removed.

M

Press at once

Span Adjustment

Digital Indicator / Bargraph

S

SET

S

M

Increase / Decrease

Span Adjustment

Digital Indicator Only

Complete

S

ON

P

SET

M

Increase / Decrease

Decimal Point Position

Complete

P

Summary of Contents for 48NDV

Page 1: ...system The user may have to review the CE or UKCA requirements in regard to the whole system and employ additional protective measures to ensure the CE or UKCA conformity In order to enable the operator to turn off the power in put immediately install a switch or a circuit breaker ac cording to the relevant requirements in IEC 60947 2 and properly indicate it POWER INPUT RATING OPERATIONAL RANGE L...

Page 2: ...STERED MOUNTING Not conform to degree of protection IP65 1 0 61 5 min USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel cutout size is as specified in the unit s data sheet 31 5 138 mm Three types of bezels are selectable when ordering Standard type Fits into M System s 48 Series panel cutout 38 139 5 mm Option D type Fits...

Page 3: ...nd below the unit for ventilation Bracket TERMINAL CONNECTIONS Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit EXTERNAL DIMENSIONS unit mm inch 75 2 95 103 4 06 10 39 18 71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16 M3 SCREW TERMINALS 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 31 1 22 100 3 94 Rounded corners for the option D OPTION D BEZEL 3 ...

Page 4: ...c PAJ PAK PBA 44 138 mm etc STANDARD BEZEL 2 10 4 41 7 5 30 3 9 15 136 5 5 37 144 5 67 11 4 45 7 5 30 4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 CONNECTION DIAGRAM ALARM OUTPUT CODE 4 4 points ALARM OUTPUT CODE 2 2 points ALARM OUTPUT CODE 0 None 1 2 12 13 14 INPUT 15 16 1 2 12 13 14 15 16 INPUT LLa 11 La LLb Lc LLc 7 8 9 8 9 10 HHa 7 Hc HHc HHb Ha HH OUT...

Page 5: ...Settings Mode Setting Selector Setting DOWN Button Switcing Detailed Settings Digital Indicator Setpoint 2 Value Setpoint 1 Value PV Indicator Note Setpoint 1 or 2 provided only for the multi color bar type ALARM OUTPUT CODE 0 None SET ENTER Button H Setpoint Adj Alarm Function Span Adj Setting Decimal Point Position Moving Average Brightness Adj Zero Adj Setting L Setpoint Adj Alarm Function Sett...

Page 6: ...Delay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjustment Digital Indicator Bargraph Z SET Z M Increase Decrease Zero Adjustment Digital Indicator Only Complete Z ON LED OFF SPAN ADJUSTMENT Apply 100 input signal before adjustment All alarm setpoints ...

Page 7: ...itched to continuous ON state 4 Press UP or DOWN buttons until the bargraph shows 100 and the digital indicator comes to a desired value and press SET DIGITAL INDICATOR SPAN ADJUSTMENT 1 Hold down M for 3 seconds and push M to choose S 2 Press UP or DOWN buttons until the digital indicator comes to a desired value and press SET DECIMAL POINT POSITION 1 Hold down M for 3 seconds and push M to choos...

Page 8: ...ibration adjust the output as explained in the following HOW TO CALIBRATE THE OUTPUT INDICATION Use a signal source and measuring instruments of sufficient accuracy level Turn the power supply on and warm up for more than 10 minutes 1 ZERO Apply 0 input and adjust the bargraph and digital indicator to 0 following the each procedure ex plained in ADJUSTMENT PROCEDURE 2 SPAN Apply 100 input and adju...

Reviews: