47LHZ

P. 5 / 14

EM-9517-B Rev.4

SETTING PROCEDURE

POWER ON

■ 

GENERAL SETTING FLOWCHART

*

1. Optional settings for parameters in a broken-line section.

 

Alarm Setting Mode is locked with no-alarm-output type. 

POWER ON

*

1

 

INITIAL SETTING FLOWCHART

Initial Setting Complete

Measuring Started

Hold down Scale/    button for 3 seconds or more to move on to Scaling Setting Mode.

Choose an input type and display scale values.

Hold down Alarm/    button for 3 seconds or more to move on to Alarm Setting Mode.

Go through the alarm settings.

Hold down Alarm/   + Scale/    buttons at once for 3 seconds or more 

to move on to Advanced Setting Mode.  Go through the advanced settings.

Hold down Alarm/    button or Scale/    button for 1 second or more

to go back to Measuring Mode.

If necessary, hold down Max/Min Alarm/    buttons at once

for a preset time duration to enter Lockout Setting Mode.

Go through the lockout settings.

Measuring Mode

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Scale/    button

for ≥3 seconds

Measuring

Measuring stopped

*

3

Mode transition

*

1. Preset time can be specified with “Transition Time to Lockout Setting Mode” in Advanced Setting Mode.

*

2. Alarm Setting Mode is locked with no-alarm-output type. 

*

3. The last measured values or status are held for DC and alarm outputs while the measuring is stopped.

 

(Except the analog output adjustments during the loop test and the scaling)

Scaling Setting Mode

Alarm Setting Mode

Advanced Setting Mode

Hold down Alarm/    or Scale/   

button for ≥1 second

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Max/Min + Alarm/    buttons at once

for a preset time duration

*

1

 

Hold down Alarm/   + Scale/    buttons at once

for ≥3 seconds

Lockout Setting Mode

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Alarm/    button

for ≥3 seconds

Loop Test Output Mode

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Alarm/   + Scale/    + Shift buttons at once

for ≥5 seconds

*

2

Summary of Contents for 47LHZ

Page 1: ...3 and properly indicate it POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 50...

Page 2: ...is tripped H turns on when the H alarm is tripped HH turns on when the HH alarm is tripped P turns on when none of the other alarms is tripped 3 Function indicators Indicate setting modes and status...

Page 3: ...ng must be in place to hold the meter Do not remove it 1 Insert the unit into the panel cutout 2 Push the mounting brackets into the grooves on both sides of the rear module until they hit the panel s...

Page 4: ...18 19 Lc LLc LLa La Hc HHc Ha HHa LL OUTPUT L OUTPUT H OUTPUT L OUTPUT H OUTPUT HH OUTPUT 9 10 POWER U V ALARM SUFFIX CODE 2 SPDT contact 2 points 9 10 POWER U V ALARM SUFFIX CODE 0 No alarm output 7...

Page 5: ...out Setting Mode Go through the lockout settings Measuring Mode Hold down Alarm or Scale button for 1 second Hold down Scale button for 3 seconds Measuring Measuring stopped 3 Mode transition 1 Preset...

Page 6: ...le button shifts one to the previous Changing parameters Pressing Shift button while one of the parameter settings is indicated on the display shifts the panel meter into the setting standby mode The...

Page 7: ...n Scale button for 3 seconds Hold down Alarm or Scale button for 1 second Shift Shift Alarm Scale Alarm Alarm Scale Alarm Alarm Scale Alarm Scale Alarm Shift Shift Alarm Scale Alarm Scaling Setting Mo...

Page 8: ...range 5 to 105 increasing decreasing increasing decreasing Fnc Analog output 100 adjustment Analog output 100 adjustment adjustable range 5 to 105 Scaling setting Go through the scaling setting in the...

Page 9: ...larm Setting Mode Alarm Shift L Setpoint L Deadband L ON Delay Time 19999 19999 0000 9999 00 99 Shift Shift Alarm Alarm Alarm Alarm Alarm Alarm L Coil at Alarm RYEN RYDN Shift Alarm Alarm Shift L Trip...

Page 10: ...B B HH ON Delay Time 00 99 Shift Alarm Alarm Alarm Alarm HH Coil at Alarm RYEN RYDN Shift Alarm Alarm Shift HH Setpoint 19999 19999 Shift H Setpoint H Deadband H ON Delay Time 19999 19999 0000 9999 00...

Page 11: ...H Lo trip H coil at alarm H Coil energized at alarm H Fnc H Coil de energized at alarm D P H Fnc H P Fnc HH setpoint HH deadband hysteresis HH ON delay time HH ON delay time seconds HH Deadband hyster...

Page 12: ...lay goes back automatically to Measuring Mode if the front buttons are left untouched for the specified time period while it is in one of the setting modes except the loop test output mode With this v...

Page 13: ...1 Preset time can be specified with Transition Time to Lockout Setting Mode in Advanced Setting Mode A Scale Scale Scale Scale Scale Set value Setting Parameters A Alarm Alarm PARAMETER Alarm setting...

Page 14: ...tile memory error reading 1 If the unit does not recover its function after the initialization repairing in the factory may be required Non volatile memory error writing Increase decrease the input si...

Reviews: