![Lütze 803012 Operating Instructions Manual Download Page 20](http://html1.mh-extra.com/html/lutze/803012/803012_operating-instructions-manual_1951220020.webp)
LION Bus Coupler
▪
System Planning
21
4.4.6
Digital Input/Output Modules (SIL2)
Fig. 10: SIL2 Digital Input and Output Module
The modules capture digital input signals in the defined voltage range via galvanic
insulated input ranges. The information are transmitted via L-Bus² to the
bus
coupler.
Product
Description
Type
Part-No.
16 Digital Inputs,
DC 24...36 V
8 Digital Outputs
DC 24...110 V
SIL2
Reads 16 inputs in the
nominal voltage wide
range for battery supplies
with DC 24 V ...36 V.
Writes the information on
8 outputs.
LION-SAFE-
DI16-DO8-LV
803501
803501.XX
16 Digital Inputs,
DC 72...110 V
8 Digital Outputs
DC 24...110 V
SIL2
Reads 16 inputs in the
nominal voltage wide
range for battery supplies
with DC 24 V ...36 V.
Writes the information on
8 ouputs.
LION-SAFE-
DI16-DO8-HV
803502
803502.XX
LB
MS
I9
I1
I3 I4 I5 I6 I
7
I8
Q4
I
GND
B
Q4
O
I2
I11 I12 I13 I14 I15 I16 GND
D
I10
I10
I9
Q5
I12
I11
Q6
I14
I13
Q7
I16
I15
Q8
I2
I1
Q1
I4
I3
Q2
I6
I5
Q3
I8
I7
Q4
LION SAFE DI/DO
X10
X11
X20
X30
X 1
3
GND
A
GND
C
Q3
O
Q3
I
Q2
G
Q2
O
Q2
I
Q1
G
Q1
O
Q1
I
Q5
O
Q6
I
Q6
O
Q6
G
Q7
I
Q7
O
Q8
I
Q8
O
Q5
G
X21
Q5
I
8
This module (digital input/output modules - SIL2) cannot perform a safe
function in conjunction with the SIL0 bus coupler. This means a
maximum of SIL0, but this module provides considerably more
diagnostic information than a SIL0 module.