LION Bus Coupler
▪
System Planning
17
4.4.1
Bus Coupler Ethernet TRDP (SIL0)
Fig.5: Bus coupler
The Bus Coupler Ethernet (SIL0) can be a gateway to a superior network, like the
vehicle control, or it can be connected via fieldbus to a PLC.
The fieldbus protocol is TRDP. Via the fieldbus data can be transmitted or
received to or from LION I/O modules.
4.4.2
Digital Input Modules (SIL0)
Fig.6: Digital Input Modules
The modules capture digital input signals in the defined voltage range via galvanic
insulated input ranges. The information are transmitted via L-Bus² to the bus
coupler. The modules are supplied via internal bus.
Product
Description
Type
Part-No.
Bus coupler
Ethernet, SIL0
Connects the LION
System to a TRDP
Fieldbus system.
LION-BC-ETH-
LUE
803012
803012.XX
CH1
X50
C2
H
X60
LION BC ETH
MS
LB
ACT1
ACT2
NS
LNK1
LNK2
CH1
X50
C 2
H
X60
LION BC ETH
MS
LB
ACT1
ACT2
NS
LNK1 LNK2
Product
Description
Type
Part-No.
16 Digital Inputs
DC 24...36 V,
SIL0
Reads 16 inputs in
the nominal voltage
wide range for
battery supplies.
LION-DI16-24V-36V
803101
803101.XX
16 Digital Inputs
DC 72 ...110 V,
SIL0
Reads 16 inputs in
the nominal voltage
wide range for
battery supplies.
LION-DI16-72V-110V
803102
803102.XX