Operating Instructions EtherCAT-Gateway
Ethercat-Gateway 716456_110_HB_EN.Docx
23
2.4.10.21
Setting current range, (I)
(2209
h
)
index
Name
Data type
R/W
Type 1
Type 3
Default
2209
h
Setting current range, (I)
USINT
r
r/w
1 - Delivery state
This index serves to set the required current range for type 3. this type does not have any rotary
switches and can only be set via the bus and LOCC-Pads.
Decimal value 1-10 = Current range 1-10A
2.4.10.22 Setting characteristics, (C) (220A
h
)
index
Name
Data type
R/W
Type 1
Type 3
Default
220A
h
Setting characteristics, (C)
USINT
r
r/w
1 - Delivery state
This index serves to set the required characteristics for type 3. this type does not have any rotary
switches and can only be set via the bus and LOCC-Pads.
Decimal value 1-10 = Characteristics 1-10
2.4.10.23 Cycle time of the query in ms (2400
h
)
index
Name
Data type
R/W
Type 1
Type 3
Default
2400
h
Cycle time of the query in ms
UINT
r/w
-
This index sets the time period within which an LOCC-Box-Net module can be queried. The cycle time
can be set between 15ms … 500ms in the gateway and applies for all modules.
Example:
Integer: 30 = 30ms
2.4.10.24 Reset and automatic issue of the node number (2800
h
)
index
Name
Data type
R/W
Type 1
Type 3
Default
2800
h
Reset and issue of the node number
USINT
w
-
Incorrect settings can lead to unwanted functions of the LOCC-Box-Net!
This index carries out a reset of all existing node numbers (>0) that are in the
LOCCbus and immediately starts the automatic issue of new node numbers. During the automatic
issue of a node number all LOCC-Box-Net modules flash. By pressing the device button, the smallest
node number (1) is assigned to the selected module and stops flashing. All other modules continue to
flash and the next mode number 2 can be issued. This process is continued until all modules stop
flashing.
This process cannot be stopped until all modules have been assigned a node number.
Activation is achieved by writing an integer value > 0
2.4.10.25 Query 'Status node number' (2801
h
)
index
Name
Data type
R/W
Default