Technical data
Rating plate
11
© Lutz-Jesco GmbH 2015
Subject to technical changes.
150413
BA-24721-02-V01
Chlorine gas changeover unit C 7523
Operating instructions
5 Technical data
Description
Value
Throughput
up to 80 kg/h Cl2 (see tab. 7)
Operating pressure
-1…0 bar
Contact gauge
Ø63 mm, class 2.5, -1…0 bar
Setting range of the switching point on the contact gauge
-0.9…-0.1 bar
Changeover time
approx. 22 s
Material in contact with the media
PVC / FPM / Silver /
coated brass
Further materials
Coated steel, PP, ABS
Voltage supply
115…230 V, 50…60 Hz
Power consumption
Normal mode
max. 0,3 A / max. 20 VA
Switch-on current
max. 17.5 A (peak)
Load capacity of the relay
max. 3 A / 250 VAC
Weight
without mounting plate
approx. 5 kg
with mounting plate
approx. 7 kg
Protection class
IP 65
Ambient temperature
0 – 55 °C, avoid direct sunlight
Air humidity
max. 95%, non condensing
Table 6: Technical data
Product
Hydraulic connections
Max. flow rate
C 7523-4K
hose 8/12 mm
4 kg/h Cl2
C7523-10K
hose 12/16 mm
10 kg/h Cl2
C7523-40K
Pipe DN25/Ø32
40 kg/h Cl2
C7523-80K
Pipe DN32/Ø40
80 kg/h Cl2
Table 7: Maximum flow