Operation
Tank change
26
© Lutz-Jesco GmbH 2015
BA-24721-02-V01
Chlorine gas changeover unit C 7523
Operating instructions
10 Operation
In normal operation, the device operates automatically and does not
require operation. The change to the standby battery is performed
automatically.
10.1 Tank change
To enable interruption-free dosing, the empty chlorine tank must be
replaced by full chlorine tanks.
Precondition for action:
ü
The control shows "empty" for a supply battery. The battery empty
LED (red) illuminates.
ü
Full chlorine tanks are available.
Perform the following working steps:
1.
Replace the empty chlorine tanks with full chlorine tanks. A
description of how to change the tanks is provided in the operating
instructions of the device which is connected directly to the chlorine
tank.
2.
Press the "OK" button on the control of the changeover unit.
è
The battery empty LED (red) extinguishes.
è
The LED battery full (green) illuminates.
ü
The tank change has been performed.
10.2 Shutting down in an emergency
DANGER!
Danger to life from chlorine poisoning!
Chlorine is poisonous. In severe cases, breathing in chlorine may lead
to death. It irritates the eyes, the respiratory system and the skin.
ð
If chlorine escapes, leave the room immediately.
ð
Use sufficient personal protective equipment.
ð
If chlorine gas escapes, wear a Type 2 self-contained breathing
apparatus that complies with EN 137.
ð
Only initiate counter measures after putting on the protective
equipment.
The device must be separated from the mains supply in emergencies.
The further procedure depends on the type of accident and should be
planned and executed by professional personnel.
10.3 Inspection intervals
The components of the chlorination installation must be subject to a daily
visual check. Inform service personnel of anything conspicuous or a
chlorine smell.