Lutz-Jesco TOPAX MC Operating Instructions Manual Download Page 34

Operation

34

© Lutz-Jesco GmbH 2020

BA-46020-02-V04

Multi-Channel Controller 

TOPAX

®

 MC

Operating instructions

Configure switching via ECO control

A limit value control is defined for the "Economy mode”. The limit value 
control is generally used to reduce the circulation capacity.

If the measured values are located within the setpoints, the output is 
closed. If the digital input is also switched for switching to another refer-
ence set, “Economy mode” is active and the switch will be made to the 
desired reference set.

Pre-conditions for actions:

ü 

The limit value control is configured as described in section “Limit 
value control” on page 24.

To configure, working in the “Setpoints” menu item, select the “Switch-
ing” tab. 

Perform the following work steps:

1.  Automatically switching the reference sets:

 Set a checkmark 

here.

2.  Switch-over: 

Select “Switching input”.

3.  Function: 

Select “ECO control”.

4.  Reference set:

 Select the reference set to which is to be switched.

5.  Digital input: 

The digital input in use is indicated here.

ü 

Configuration "Switchover via ECO control” completed.

9.6.3.2  Switching via timer

Up to ten timers can be configured parallel to the switching via a digital 
switching input (see section 9.6.3.1 “Switching via digital inputs” on 
page  33). Times are defined for the point at which the timers should 
switch to a certain reference set.

To configure, working in the “Setpoints” menu item, select the “Switch-
ing” tab.

Perform the following work steps:

1.  Automatically switching the reference sets: 

Set a checkmark 

here.

2.  Switch-over: 

Configure up to ten timer switches and state the fol-

lowing information.

3.  Off/Active:

 Switch on the timer.

4.  Time:

 Configure a time at which the switch-over is to be made. State 

the hour and minutes.

5.  Monday – Sunday: 

Set a checkmark against every weekday on 

which the timer should be active.

6.  Reference set: 

Select the reference set to which is to be switched.

ü 

Configuration "Switchover via timer” completed.

9.7  Access via network

Accessing the device via a network requires that it is connected to an ex-
isting Ethernet or RS485 network.

Further information about connection to an existing network is specified 
in sections ü “RC protection for relay connected.” on page 17, n “Only 
use CAT5 cables or better” on page 17 and 8.4 “Network settings” on 
page 26.

i

If connection problems are experienced during access via net-
work, check the configuration of your security software.

Modbus

You can access certain data on the device via the Modubus protocol using 
both Ethernet and the RS485. You need the Modbus protocol e.g. For the 
connection with a control panel or a PLC. Modbus TCP/IP is supported for 
Ethernet and Modbus RTU is supported for the RS485 interface.

The Modbus addresses of your device are stated in section 12 “Modbus 
addresses TOPAX® MC” on page 39.

Web browser (only Ethernet)

You can access the device data using all network devices which are fitted 
with a web browser. You will require the IP address, subnetmask and pos-
sibly the MAC address of the device.

The network settings of your device are listed under Main menu > Sys-
tem > Service > Network.

Open the web browser of your end device and enter the IP address of the 
device in the address row. The page of the device will open and provide a 
range of information.

TFTP protocol (only Ethernet)

You can access the device memory via a TFTP client software as long as 
TFTP is activated in the network settings. You need the device IP address 
for access.

The network settings of your device are listed under Main menu > Sys-
tem > Service > Network.

Summary of Contents for TOPAX MC

Page 1: ...ms Lutz Jesco GmbH 2020 BA 46020 02 V04 Multi Channel Controller Operating instructions Read the operating manual The user is responsible for installation and operation related mistakes 40900001_6 nsi...

Page 2: ......

Page 3: ...2 Output modules 10 6 Dimensions 11 6 1 Outside dimensions 11 6 2 Drillhole dimensions 11 7 Installation 12 7 1 Principles 12 7 2 Installation on the wall 12 7 3 Electrical installation 12 7 4 Termina...

Page 4: ...s WARNING Refers to a potentially hazardous situation Failure to follow this instruction may lead to death or severe injuries CAUTION Refers to a potentially hazardous situation Failure to follow this...

Page 5: ...stem functions n Failure of required maintenance and repair methods n Risk to persons when working on the device n Danger to the environment from overdosing 2 3 Working in a safety conscious manner Be...

Page 6: ...regulations on accident pre vention 2 4 3 Trained persons Trained persons have received training from the operator about the tasks they are to perform and about the dangers stemming from improper be...

Page 7: ...ctivity and the control of chlorinators 3 3 Foreseeable misuse The following section provides information regarding the device applica tions which are classified as non intended use This section is in...

Page 8: ...rent module 2 Digital 1 3 Virtual 1 4 pH Redox module 1 Module for 4 20 mA signals and sensors with 24 V voltage supply 2 Digital input for the external control of a function here external stop 3 Para...

Page 9: ...Main view with three sensors Item Function 1 Login password settings 2 Date time 3 Measured values 4 Main menu 5 File Browser 6 Status row for messages Tab 5 Position numbers main view with three sens...

Page 10: ...endant on the measuring cell transconductance CS120 excess chlorine measuring cell mg l 0 10 dependant on the measuring cell transconductance Diaphragm covered measuring cell mg l 0 10 dependant on th...

Page 11: ...23 BA 46020 02 V04 Multi Channel Controller TOPAX MC Operating instructions 6 Dimensions All dimensions in mm 6 1 Outside dimensions All dimensions in mm Fig 4 Outside dimensions 6 2 Drillhole dimensi...

Page 12: ...orm the specifications of this sec tion for devices without a pre fitted Schuko plug Pre conditions for actions The device was installed in accordance with section 7 2 Installation on the wall on page...

Page 13: ...en 5 LED output 3 red 6 LED output 3 green 7 LED output 4 red 8 LED output 4 green 9 10 LED output GND Ground for the LEDs 11 Disturbance variable input 0 4 20 mA 12 13 Analogue output 1 0 4 20 mA wor...

Page 14: ...tronic distortion of the measurement results Incorrect installation of the electrical cables can distort the measure mentresults Asaresult thecontrolofconnecteddevicescanbefaulty Do not route the conn...

Page 15: ...ut Conductivity measuring conductive k 1 black BK 2 Temperature input blue BU 3 Conductivity measurement input brown BN 4 Conductivity measurement input white WH Tab 11 Clamp connection conductivity m...

Page 16: ...e output connects a servomotor with or without feedback Fig 17 Output circuit board with servomotor 20 mA Terminal Function Description 1 GND 2 Input feedback 4 20 mA 3 Output 4 20 mA Tab 20 Clamp con...

Page 17: ...ded Thus the de vice will operate in an uncontrolled manner To prevent bonding if the load circuit suffers a short circuit the relays must be protected separately on the maximum relay switching curren...

Page 18: ...onnect up to 14 devices with a PC or a PLC Modbus RTU protocol serves as a protocol for data transfer You can use the addresses 1 to 14 The addresses 0 and 15 are reserved for internal purposes and ar...

Page 19: ...utput from 0 4 20 mA for the actuation of constant actors x Servomotor with 20 mA feedback n Servomotors which are controlled via 0 4 20 mA and have a 0 4 20 mA position feedback Tab 23 Functions of t...

Page 20: ...Here you can check which water parameters are measured This setting can only be changed in the configuration as sistant 6 Unit Select the appropriate unit 7 Measuring range If an input field is availa...

Page 21: ...m and state a difference value over which the alarm will be triggered 8 Delay Set a time delay for the minimum and maximum alarm Configuration of the difference completed Combined chlorine Bound chlor...

Page 22: ...to evaluate switching statuses and to detect them as alarm message which are to be documented in the log book Perform the following work steps 1 In the main menu under System Inputs navigate to the Di...

Page 23: ...ontrollers on page 19 and in section 15 Glossary on page 47 Perform the following work steps 1 Working in the main menu under System Controller navigate to the parameter tab 2 Working in the Parameter...

Page 24: ...the measured values in which the water parameters must be located so that the output switches Press the minimum or maximum value that you wish to change Configuration of the limit value control compl...

Page 25: ...d overview completed 8 2 4 Colours of the alarm messages You can edit the colours of the different messages Perform the following work steps 1 In the main menu under System Settings navigate to the Al...

Page 26: ...ich you are logged in Password protection configured 8 4 Network settings You may need to perform settings in order to be able to use the device in a network Further information about using the device...

Page 27: ...wing logbook files Log Format Description REPORTS CSV Messages TREND DAT Trend data SERVICE CSV Service entries CHANGES CSV Changes to the configuration SETUP SET Configuration ADJUSTMENT CSV Calibrat...

Page 28: ...of the single rod measuring cell and the ideal value of the set buffer solution is displayed during calibration The response time for a new single rod measuring chain is a few sec onds and is set when...

Page 29: ...eps 1 Working in the main menu under Calibration navigate to the Sen sors tab 2 Working under sensor select the sensor that measures the pH val ue and which you wish to calibrate 3 Press the Offset bu...

Page 30: ...l set by accident set it by pinching off the measuring electrode and entering a value of zero Should real 2 point calibration be performed e g due to hot water you must first per form calibration with...

Page 31: ...re You can connect a temperature sensor to every input module You can ad just the temperature sensor by setting a reference value When setting the reference value the device will automatically correct...

Page 32: ...d runs to top speed then stops This can take a number of minutes 6 Completion of the compensation is signalled with Compensation OK Calibration of an servomotor 20 mA completed 9 5 7 2 Calibrating the...

Page 33: ...is active via a digital input 9 6 3 1 Switching via digital inputs Before you can use a digital input for switching to a particular reference set you must configure the digital input in accordance wi...

Page 34: ...at which the switch over is to be made State the hour and minutes 5 Monday Sunday Set a checkmark against every weekday on which the timer should be active 6 Reference set Select the reference set to...

Page 35: ...tion test n Calibrating the measured values Annually n Checking the button cell Tab 27 Maintenance intervals 10 2 Keeping logfiles If you make an entry in the logfiles the device will issue a reminder...

Page 36: ...equired Slotted screwdriver New fuse 5 x 20 mm 3 15 A 250 V delay Perform the following work steps 1 The fuse holder in the form of a bayonet catch is located at the bot tom right hand side above the...

Page 37: ...m the following work steps 1 Make a note of the date and scope of the maintenance performed 2 In the Service menu navigate to the Service entry tab Enter your company name and notes about the maintena...

Page 38: ...heck that the battery is really empty To do so navigate to the menu System Information System values You can view the battery voltage under Battery If the voltage is under 2 9 V change the battery n R...

Page 39: ...2001 0x3334 Address 2002 0x3536 transferred 2003 x Status of digital inputs Displays the terminal logic not the configured software function The individual bits are assigned directly to the input clam...

Page 40: ...Free entry n 255 No type 2021 2022 x Measurement Number of positions after the decimal point see unit 4 bytes signed int 2023 x Unit Number Unit decimal places 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 mA A...

Page 41: ...signed int 2034 x x Minimum and maximum alarm Write 0 clear alarm Read Bit 0 minimum alarm is active Bit 1 maximum alarm is active 2035 x x Y alarm Write 0 clear alarm Read Bit 0 Y alarm is inactive B...

Page 42: ...ut 2 Y2 only manual mode 2107 2108 x x Setpoint 1 Number of positions after the decimal point see unit 4 bytes signed int 2109 2110 x x Setpoint 2 If 2 side control is active 4 byte signed int 2111 x...

Page 43: ...Virtual 4 maximum alarm Sensor 1 minimum alarm Sensor 2 minimum alarm Sensor 3 minimum alarm Sensor 4 minimum alarm 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2226 x Alarm status 2 If the bit is set the a...

Page 44: ...nput 6 Digital input 7 Digital input 8 Sensor 1 calibration not OK Sensor 2 calibration not OK Sensor 3 calibration not OK Sensor 4 calibration not OK Temperature 1 calibration not OK Temperature 2 ca...

Page 45: ...uaci n cumple con los requisitos sanitarios y de seguridad vigentes de las directivas de la U E citadas a continuaci n Esta declaraci n ser invalidad por cambios en el aparato realizados sin nuestro c...

Page 46: ...r Company Phone Date Address Contact person Manufacturer order no Date of delivery Device type Serial number Nominal capacity nominal pressure Description of fault Service conditions of the device Poi...

Page 47: ...P PI or PID controller indi cates the amount by which the actual value X must deviate from the setpoint W so that the variable Y 100 If the control deviation X W is lower the control variable is also...

Page 48: ...stallation Connecting the actors 15 Connecting the sensor 14 Installation example 8 Installation on the wall 12 Intended purpose 7 Intended use 7 Internal fuse 36 L Logbook 27 M Maintenance 35 Mainten...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...ge 19 D 30900 Wedemark Phone 49 5130 5802 0 info lutz jesco com www lutz jesco com Multi channel controller TOPAX MC Operating instructions Copyright 2020 by Lutz Jesco GmbH 40900001_6 nsicht Gaswarng...

Reviews: