QS Link Wiring
3
3.1
Link Rules
The following Link rules must be observed for proper operation.
- Maximum of 100 devices (such as a
GRAFIK Eye
®
QS Unit, QS keypad,
QSPS-P2-10-60, or Sivoia
®
QS shade)
- Maximum of 100 zones (such as a
Sivoia
QS shade, or a lighting zone on a
GRAFIK Eye
QS Unit)
- Maximum 600 m (2000 ft.) of cable connecting all QSPS-P2-10-60 panels
- Maximum 600 m (2000 ft.) of cable to devices wired to each QSPS-P2-10-60
- Use only cable with at least one twisted/shielded pair for communications (MUX and MUX)
3.2
Wire Length Chart
Maximum devices per one output
Maximum distance per one output based on wire guage
Controls
12 AWG
(4 mm
2
)
16 AWG
(1.5 mm
2
)
18 AWG
(1 mm
2
)
GRX-CBL-346S-500
None
Up to 8
seeTouch QS
keypads
1200 ft (350 m)
500 ft (150 m)
300 ft (75 m)
1
Sivoia
QS roller 64
TM
,
roller 100, roller 200CW,
or roller 225
TM
Up to 1
seeTouch QS
keypad
500 ft (150 m)
200 ft (60 m)
125 ft (35 m)
2
Sivoia
QS roller 64,
≤ 30 sq ft
(2.75 sq m) each
None
200 ft (60 m)
75 ft (20 m)
50 ft (15 m)
3
Sivoia
QS roller 64,
≤ 20 sq ft
(1.8 sq m) each
None
2
Sivoia
QS roller 100,
≤ 50 sq ft
(4.6 sq m) each
None
Page 4
Sivoia
®
QS
QSPS-P2-10-60 (CE)
Installation instructions
Summary of Contents for QSPS-P2-10-60
Page 1: ...QS Smart Power Supply Panel CE Installation Instructions QSPS P2 10 60 ...
Page 12: ...Page 11 Sivoia QS QSPS P2 10 60 CE Installation instructions Notes ...
Page 13: ...Page 12 Sivoia QS QSPS P2 10 60 CE Installation instructions Notes ...
Page 14: ...Page 13 Sivoia QS QSPS P2 10 60 CE Installation instructions Notes ...