S P E C I F I C A T I O N   S U B M I T T A L

369653b   8   05.04.12

Occupant Sensors

LOS-CDT Series

Sensors

Sensor Adjustments

Timer Test Mode

Factory Settings

1. Remove the retainer cover.
2. Rotate the black timer adjustment knob to 

 about midway (12 o’clock).

3. Return setting to minimum setting (full CCW).

   Note: The timer will remain in the 8-second test

 mode for 1 hour, then automatically reset to 
 8 minutes.

4.  To manually take the timer out of the 8-second test 

mode, turn the timer adjustment approximately 
1/16 in (1.5 mm)   clockwise to make the setting 
slightly above minimum (just above the 8-minute 
setting).

Factory Settings

12 o’clock

Full CCW

Auto/Manual

Threshold

LED Motion Indicator

Reset Learned Settings

Strong Airflow Compensation

Over Doorway Installation

Timer Adjust

Auto Sensitivity

     Off (Default) 

 

 

 

On

Automatic (Normal) 

 

     Manual on/off (Override)

Auto Threshold Adjustment 

     High Sensitivity (Low turn-on threshold)

Lights indicate motion  

     Disable LED Indicator 

Retain Settings  (Normal) 

     Erase all learned settings,

 

 

 

 

     restart Learning (Toggle On)

 Off 

   On

Disable Compensation  (Normal)   Enable Compensation 
No (Normal) 

 

 

     Yes (Use increased turn-on threshold)

Adjust Timer Automatically 

     Use Manual Setting (No adjustment)

Adjust Sensitivity Automatically    Adjust Sensitivity Manually

ON

ON

A

1

2

3

4

B

1

2

3

4

Override Settings

ON

ON

ON

ON

A

   1

   2

   3

   4

B

1

2

3

4

Black: Timer 
8 min

Blue: Photo 
cell (R model 
only)
100% default

Red: Infrared 
sensitivity 
75% default

Green: 
Ultrasonic 
range 
50% default

8

Summary of Contents for LOS-CDT Series

Page 1: ...aved in protected memory are not lost during power outages 500 to 2000 sq ft 46 to 186 m2 coverage when mounted on an 8 12 ft 2 4 to 3 7 m ceiling 180 and 360 field of view Affords choice of turning l...

Page 2: ...pen collector when unoccupied Operating Environment Temperature 32 to 104 F 0 to 40 C Relative humidity less than 95 non condensing For indoor use only Adaptive Functions Installation 60 minutes Learn...

Page 3: ...g control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoSystem No GRAFIK 5000 6000 7000TM No when used with seeTouch wallstations w...

Page 4: ...common Black White Red Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliar...

Page 5: ...y Common Gray wire logic with photo cell active Room First Occupied During Occupancy Light level Lights Light level Lights Below set value Turn on Falls below set value Turn on Above set value Remain...

Page 6: ...orway so that traffic in a hallway will not affect the sensor otherwise place in center of room Closely follow the diagrams shown concerning major and minor motion coverage The sensor can detect major...

Page 7: ...d mounting post onto cover plate Drill through ceiling tile with assembly using cutter end of the threaded mounting post Secure with washer and nut Cutter end Mounting to Non Standard Ceiling or Fixtu...

Page 8: ...o clock Full CCW Auto Manual Threshold LED Motion Indicator Reset Learned Settings Strong Airflow Compensation Over Doorway Installation Timer Adjust Auto Sensitivity Off Default On Automatic Normal M...

Page 9: ...ghts Out Move from underneath the sensor and remain still until the lights turn off Move around normally to turn the light on 4 Adjust to desired level If lights remain off adjust the blue knob anothe...

Reviews: