S P E C I F I C A T I O N   S U B M I T T A L

369653b   7   05.04.12

Occupant Sensors

LOS-CDT Series

Sensors

Installation

Mounting Plate Dimensions

4.2 in 
(106.6 mm)

2.5 in 

(63 mm)

.52 in 

(13.3 mm)

Using the Infrared Mask

Center Ceiling Mount

(Mask blocks sensor seeing 

out doorway into hall)

Corner Ceiling Mount

(No mask needed)

Conference 

Room Mask

180° Mask

Full Mask

Rectangular 

Areas

Over the Door

Specific Areas 

You Wish to 

Mask

Mounting

Normal Mounting
Twist and lock threaded mounting post onto cover 
plate. Drill through ceiling tile with assembly, using 
cutter end of the threaded mounting post. Secure 
with washer and nut.

Cutter end

Mounting to Non-Standard Ceiling or Fixture
Mount twist-lock cover plate using mounting 
screws, nuts, and washers (included). Drill/punch 
wire routing hole through ceiling tile at center of 
cover plate.

13/16 in (21 mm)

Typical Mask Patterns

Wire Lengths

# Sensors 

  1 

  2 

  3 

  1 

  2 

  1

# Aux. PP 

  0 

  0 

  0 

  1 

  1 

  2

22 AWG 

750 ft  375 ft  250 ft  375 ft  250 ft  250 ft

0.5 mm

2

 

365 m  180 m  120 m  90 m 

120 m  120 m

20 AWG 

1200 ft  600 ft  400 ft  600 ft  400 ft  400 ft

0.75 mm

2

 

730 m  365 m  240 m  365 m  240 m  365 m

18 AWG 

2400 ft  1200 ft  800 ft  1200 ft  800 ft  800 ft

7

Summary of Contents for LOS-CDT Series

Page 1: ...aved in protected memory are not lost during power outages 500 to 2000 sq ft 46 to 186 m2 coverage when mounted on an 8 12 ft 2 4 to 3 7 m ceiling 180 and 360 field of view Affords choice of turning l...

Page 2: ...pen collector when unoccupied Operating Environment Temperature 32 to 104 F 0 to 40 C Relative humidity less than 95 non condensing For indoor use only Adaptive Functions Installation 60 minutes Learn...

Page 3: ...g control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoSystem No GRAFIK 5000 6000 7000TM No when used with seeTouch wallstations w...

Page 4: ...common Black White Red Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliar...

Page 5: ...y Common Gray wire logic with photo cell active Room First Occupied During Occupancy Light level Lights Light level Lights Below set value Turn on Falls below set value Turn on Above set value Remain...

Page 6: ...orway so that traffic in a hallway will not affect the sensor otherwise place in center of room Closely follow the diagrams shown concerning major and minor motion coverage The sensor can detect major...

Page 7: ...d mounting post onto cover plate Drill through ceiling tile with assembly using cutter end of the threaded mounting post Secure with washer and nut Cutter end Mounting to Non Standard Ceiling or Fixtu...

Page 8: ...o clock Full CCW Auto Manual Threshold LED Motion Indicator Reset Learned Settings Strong Airflow Compensation Over Doorway Installation Timer Adjust Auto Sensitivity Off Default On Automatic Normal M...

Page 9: ...ghts Out Move from underneath the sensor and remain still until the lights turn off Move around normally to turn the light on 4 Adjust to desired level If lights remain off adjust the blue knob anothe...

Reviews: