S P E C I F I C A T I O N   S U B M I T T A L

369653b   6   05.04.12

Occupant Sensors

LOS-CDT Series

Sensors

Installation

Sensor Placement

Range Diagrams

• The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall 

cabinets, shelves, indirect hanging fixtures, etc.

• Do not place sensor within 6 ft (1.8 m) of air vents, air handlers, windows, fans, etc., as this may cause 

false triggering.

• If installing a 180° occupant sensor (500 and 1000 models), place the sensor on the same wall as the 

doorway so that traffic in a hallway will not affect the sensor; otherwise, place in center of room.

• Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect 

major motion (such as a person taking a half-step) at a greater distance than it can detect minor motion 
(such as writing or typing at a desk).

• Decrease total coverage area by 15% for “soft” rooms (for example, heavy draperies or heavy carpeting).

LOS-CDT-500

64 ft (19.5 m)

45 ft (13.7 m)

23 ft

 (7 m)

32 ft

(9.8 m)

Major motion detection

Minor motion detection

22 ft (6.7 m)

16 ft (4.9 m)

12 ft (3.7 m)

22 ft (6.7 m)

23 ft 

(7 m)

32 ft

 (9.8 m)

32 ft (9.8 m)

23 ft (7 m)

23 ft  

(7 m)

32 ft 

(9.8 m)

12 ft (3.7 m)

22 ft (6.7 m)

12 ft (3.7 m)

22 ft (6.7 m)

LOS-CDT-1000

LOS-CDT-2000

6

Summary of Contents for LOS-CDT Series

Page 1: ...aved in protected memory are not lost during power outages 500 to 2000 sq ft 46 to 186 m2 coverage when mounted on an 8 12 ft 2 4 to 3 7 m ceiling 180 and 360 field of view Affords choice of turning l...

Page 2: ...pen collector when unoccupied Operating Environment Temperature 32 to 104 F 0 to 40 C Relative humidity less than 95 non condensing For indoor use only Adaptive Functions Installation 60 minutes Learn...

Page 3: ...g control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoSystem No GRAFIK 5000 6000 7000TM No when used with seeTouch wallstations w...

Page 4: ...common Black White Red Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliar...

Page 5: ...y Common Gray wire logic with photo cell active Room First Occupied During Occupancy Light level Lights Light level Lights Below set value Turn on Falls below set value Turn on Above set value Remain...

Page 6: ...orway so that traffic in a hallway will not affect the sensor otherwise place in center of room Closely follow the diagrams shown concerning major and minor motion coverage The sensor can detect major...

Page 7: ...d mounting post onto cover plate Drill through ceiling tile with assembly using cutter end of the threaded mounting post Secure with washer and nut Cutter end Mounting to Non Standard Ceiling or Fixtu...

Page 8: ...o clock Full CCW Auto Manual Threshold LED Motion Indicator Reset Learned Settings Strong Airflow Compensation Over Doorway Installation Timer Adjust Auto Sensitivity Off Default On Automatic Normal M...

Page 9: ...ghts Out Move from underneath the sensor and remain still until the lights turn off Move around normally to turn the light on 4 Adjust to desired level If lights remain off adjust the blue knob anothe...

Reviews: