Energi Savr Node
TM
0-10V / SoftSwitch
®
Installation Guide
Lutron
®
|
6
Energi Savr Node
TM
0-10 V / SoftSwitch
®
|
Installation Guide
Occupancy Sensor
IR Transmitter
IR Transmitter
Daylight/IR Sensor*
Note:
Maximum wire run
length to each input not
to exceed 150 ft (46 m).
IR Receiver*
or Wired
Wallstation*
NEC
Class 2
Dry Contact
Switch
Red
Black
Yello
w
Blue
Black
Red
Red
Black
White*
White*
20 V – 20 V
Occ – Occupancy Sensor
Photo – Daylight Sensor
IR – IR Receiver*
Switch –
NEC
Class 2/PELV Switch
Com – Common
LU
TR
O
N
R
LUT
RON
LU
TR
O
N
R
Step 4: Input group wiring
To connect a daylight sensor, occupancy sensor, infrared (IR) receiver, and/or NEC
®
Class 2/PELV dry contact switch, refer to the
instruction sheets provided with the devices. Diagrams for the input terminals are shown below.
WARNING! Danger of Shock. May result in serious injury or death.
DO NOT WIRE WHEN LIVE! Switch off power to all power
feeds via circuit breaker before wiring or servicing the
Energi Savr Node
unit.
Buttons and LEDs in the unit are used for programming and troubleshooting. If line voltage shield is removed, the unit must
be accessed by a certified electrician, following local codes.
Note: The
Energi Savr Node
unit
accepts only one IR input (either daylight/IR sensor or IR receiver) per group.
Input Group Wiring:
• 20 AWG to 12 AWG
(0.5 mm
2
to 4.0 mm
2
)
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lbs (0.5 N
•
m)
NOTE:
There are four input groups. Each group has the same
inputs as shown in the diagram below.
Input Group Wiring
* Note:
Only one IR device may be connected per input. If the IR signal from
a daylight sensor is connected, a wall control may not be connected to the
same input, and vice-versa.
Line Voltage Shield