Energi Savr Node

TM

 0-10V / SoftSwitch

®

 Installation Guide

Lutron

®

  

|

  4

Energi Savr Node

TM

 0-10 V / SoftSwitch

®

 

|

 Installation Guide

Step 3: Load wiring

The 

Energi Savr Node 

unit

 

operates at 120-277 V . Use the following instructions to wire line voltage loads to the 

Energi Savr Node 

unit.

WARNING! Danger of Shock. May result in serious injury or death.

 DO NOT WIRE WHEN LIVE! Switch off power to all power 

feeds via circuit breaker before wiring or servicing the 

Energi Savr Node 

unit.

The

 Energi Savr Node 

unit is a feed-through device. This means that each switched output needs the Line and Load wires. THERE IS 

NO INTERNAL CONNECTION BETWEEN THE CONTROL POWER TO THE UNIT AND THE SWITCHED OUTPUTS.

Zone Switching:

120-277 V

0-10 V Zones:

(QSN-4T16-S only)

Feed-Through Wiring Example 1 – 4 Circuits, Multiple Feeds

Switched Hot (1B)

Hot F

eed (1A)

Hot F

eed (2A)

Hot F

eed (3A)

Hot F

eed (4A)

Switched Hot (2B)

Switched Hot (3B)

Switched Hot (4B)

Ground Bar

Neutral Wires

Distribution 

Panel

LOAD

LOAD

LOAD

LOAD

0-10 V Wiring (QSN-4T16-S only)

• 20 AWG to 12 AWG (0.5 mm

2

 to 4.0 mm

2

)

• Strip length: 1/4 in (6 mm)
• Torque: 5 in

-lbs (0.5 N

m)

• 

Connect only NEC

®

 Class 2/PELV circuits or connect 

only non-

NEC

 Class 2/PELV circuits to 0-10 V zones 

1-4.

• 0-10 V zones 1-4 are not isolated from each other.
• Negative (–) terminals are not internally connected 

to each other—both positive (+) and negative (–) 

connections must be made.

• Follow all national and local codes for separation 

requirements.

Load Wiring:

• Two (2) 14 AWG to 

12 AWG (2.5 mm

2

 to 

4.0 mm

2

)

• Strip length: 3/8 in 

(8.5 mm)

• Torque: 7 in-lbs 

 

(0.79 N

m)

0-10 V Wiring

(QSN-4T16-S only)

Hot

Hot

Hot

Hot

Neutral
Neutral
Neutral
Neutral

Ground

Ground

Summary of Contents for Energi Savr Node QSN-4S16-S

Page 1: ...re inputs 7 QS link wiring 8 Applications 10 Out of box functionality 10 Normal operation 11 QS link input s setup 11 Troubleshooting 11 Warranty 12 Contact information 12 System Example Programming Guide available at www lutron com softswitchenergisavrnode QS link Control Power 120 277 V 4 Load Input Feeds 120 277 V 4 0 10 V Channels QSN 4T16 S only Emergency Contact Closure Input Contact Closure...

Page 2: ...rgency contact closure input defaults to Emergency Mode in the absence of a contact closure across the input The QS Link can have up to 100 zones and 100 devices The Energi Savr Node unit counts as 1 device and 4 zones on the QS link In a system with multiple Energi Savr Node units on a QS link a maximum of 100 daylight sensors 100 occupancy sensors 100 IR receivers and 100 Pico wireless controlle...

Page 3: ...ltage to power the Energi Savr Node unit WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all power feeds via circuit breaker before wiring or servicing the Energi Savr Node unit Buttons and LEDs in the unit are used for programming and troubleshooting If wiring is exposed when accessing buttons and LEDs the unit must be accessed by a certifie...

Page 4: ...0 10 V Zones QSN 4T16 S only Feed Through Wiring Example 1 4 Circuits Multiple Feeds Switched Hot 1B Hot Feed 1A Hot Feed 2A Hot Feed 3A Hot Feed 4A Switched Hot 2B Switched Hot 3B Switched Hot 4B Ground Bar Neutral Wires Distribution Panel LOAD LOAD LOAD LOAD 0 10 V Wiring QSN 4T16 S only 20 AWG to 12 AWG 0 5 mm2 to 4 0 mm2 Strip length 1 4 in 6 mm Torque 5 in lbs 0 5 N m Connect only NEC Class 2...

Page 5: ...mm2 to 4 0 mm2 Strip length 1 4 in 6 mm Torque 5 in lbs 0 5 N m Connect only NEC Class 2 PELV circuits or connect only non NEC Class 2 PELV circuits to 0 10 V zones 1 4 0 10 V zones 1 4 are not isolated from each other Negative terminals are not internally connected to each other both positive and negative connections must be made Follow all national and local codes for separation requirements Loa...

Page 6: ...he input terminals are shown below WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all power feeds via circuit breaker before wiring or servicing the Energi Savr Node unit Buttons and LEDs in the unit are used for programming and troubleshooting If line voltage shield is removed the unit must be accessed by a certified electrician following l...

Page 7: ...ollow all applicable national and local codes for proper circuit separation and protection CCI input must be used with dry contact closure devices If the Emergency input is open the Energi Savr Node unit will enter Emergency Mode which will turn on all loads and disable local zone control and control from sensors and QS devices Note The Energi Savr Node unit will default to Emergency Mode if the E...

Page 8: ...shielded from Belden model 9461 Check for compatibility in your area A QS system can have up to 100 zones and 100 devices The Energi Savr Node unit counts as 1 device and up to 4 zones See diagram on the right for QS link wiring 1 Connect terminals 1 3 and 4 to all Energi Savr Node units 2 Each Energi Savr Node unit has its own built in power supply 3 The terminal 2 connection 24 V supplies power ...

Page 9: ...nstallation Guide Energi Savr Node unit Sivoia QS Shade Sivoia QS Smart Power Panel seeTouch QS Wallstations QS Control Link Sivoia QS Smart Power Panel Sivoia QS Shade seeTouch QS Wallstations Energi Savr Node unit QS Control Link QS Link Wiring continued Daisy chain Wiring Example T tap Wiring Example ...

Page 10: ... level QSN 4T16 S only Corresponding zone light levels will raise or lower when light sensed by daylight sensor falls or rises based on a factory default setting IR Receivers IR See IR Receiver literature for compatible transmitters Corresponding zones respond to on off and Scene commands from compatible IR transmitters QSN 4T16 S only Corresponding zones respond to Raise and Lower commands from c...

Page 11: ...it for 3 seconds Note For more advanced programming information refer to the online Programming Guide at www lutron com softswitchenergisavrnode Using LEDs to troubleshoot WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all power feeds via circuit breaker before wiring or servicing the Energi Savr Node unit Buttons and LEDs in the unit are us...

Page 12: ... TO MEET ANY DUTY INCLUDING OF GOOD FAITH OR OF REASONABLE CARE NEGLIGENCE OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED TO THE INSTALLATION DEINSTALLATION USE OF OR INABILITY TO USE THE UNIT OR OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY OR ANY AGREEMENT INCORPORATIN...

Reviews: