Load Wiring (continued)
Feed-Through Wiring Example 2 – 4 Circuits, Single Feed
Zone Switching:
120-277 V
0-10 V Zones:
(QSN-4T16-S only)
Hot
Neutral
Ground
Ground Bar
“A” Terminals Jumpered
Neutral Wires
Distribution
Panel A
LOAD
LOAD
LOAD
LOAD
0-10 V Wiring (QSN-4T16-S only)
• 20 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lbs (0.5 N
•
m)
• Connect only NEC
®
Class 2/PELV circuits or connect only non-
NEC
Class 2/PELV circuits to 0-10 V zones 1-4.
• 0-10 V zones 1-4 are not isolated from each other.
• Negative (–) terminals are not internally connected to each
other—both positive (+) and negative (–) connections must be
made.
• Follow all national and local codes for separation requirements.
Load Wiring:
• Two (2) 14 AWG to
12 AWG (2.5 mm
2
to
4.0 mm
2
)
• Strip length: 3/8 in
(8.5 mm)
• Torque: 7 in-lbs
(0.79 N
•
m)
0-10 V Wiring
(QSN-4T16-S only)
Switched Hot (1B)
Hot F
eed (1A)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)