Dimensions and Mounting
(continued)
Top View
Left Side View
Front View
Bottom View
Right Side View
PELV
(Class 2: USA)
wiring only
Knockout for LZC link wiring
PELV (Class 2: USA)
wiring only
Knockout for main feed entry
(panel with main lugs only)
(4) conduit
knockouts for wall
control and sensor
wiring
(4) conduit knockouts for
input feeds (feed-through
panel only), switch legs, and
dimmed legs to loads
4.1
(105)
15.1
(384)
2.0 (51)
24.0
(610)
21.0
(533)
11.5
(292)
9.1
(231)
0.31 (8)
diameter
0.63 (16)
diameter
(4) keyholes for
surface
mounting
Dimensions are in inches (mm)
Knockouts are 7/8 inch (22 mm) in diameter
This page applies to:
Small
Panel
Mounting the Small Panel
PELV (Class 2:
USA) wiring
Preferred feed wiring
(panel with main lugs only)
Input feeds
(feed-through
panel only),
switch legs, and
dimmed legs to
loads
Notes
• Surface mount indoors
• Panel weighs 23 lbs. (10.4 kg).
Reinforce wall structure for weight and
local codes
• Ambient temperature: 32 °F-104 °F
(0 °C-40 °C)
• Relative humidity:
< 90% non-condensing
• Mount panel where audible noise is
acceptable (internal relays click)
• Mount panel within 7° of vertical
• Lutron recommends 1/4 in. (6 mm)
mounting bolts
• Cover overhangs enclosure by 3/4 in.
(19 mm)
Side View
Front View
R
6
Installation Guide for Lighting Zone Controllers