Installation Guide for Lighting Zone Controllers 21
This page applies to:
LZC1
Small
Panel
Std.
Panel
Installing Wall Controls
MW-V Wiring Instructions
Turn power OFF to the LZC or LZC panel before
connecting wall controls.
• Lights can be dimmed or switched ON/OFF from the
MW-V
• Lights can be switched ON/OFF to the MW-V preset
level from the VETS-P
• Wire size #18 AWG (1.0 mm
2
)
• Maximum wire length is 250 ft. (76 m)
• Wall controls are PELV (Class 2: USA) devices. Do
nut run their wires in the same conduit as line
voltage.
LUTRON
Q P 7 6 5 4 3 2 1
LUTRON
LUTRON
VETS-P
VETS-P
MW-V or
MW-VETS
Blue
Blue
Blue
Blue
Terminal
block on
back of
MW-V
To additional LZCs
(total of 3 LZCs
maximum)
Maximum of 9
VETS-P controls
To WC COM
To WC SIGNAL
To +24 V
To CIR COM
1
2
3
4
5
6
7
8
9
3: CIR COM
4: WC COM
5: WC SIGNAL
6: +24 V
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
1 2 3 4 5 6 7 8 9 1
0
1 2 3 4 5 6 7 8 9 1
0
CLASS 2 LOW VOL
T AGE WIRING
+24V
PS Signal
PS Com
Circuit Com
WC Com
WC Signal
+24V
+15V
OCC Signal
OCC Com
MUX
MUX
Link Com
EMERG
Shield
Digital Link
Enlace Digital
Lien Digital
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer to
the Digital microWATT
Hardware Installer's
Guide (p/n 031-268).
Para la instalación,
consulte la Guía del
Instalador de Digital
microWATT Hardware
(p/n 031-268).
Pour installation, référer au
guide pour quincaillerie
Digital microWATT
(p/n 031-268) de
l'installateur.
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
1-610-282-0298 www.lutron.com
Mexico
1
-888-235-2910
1-610-282-1243 www.lutron.com
Coopersburg, PA 18036 USA
DMW-LZC1
R
TEL
FAX
R
LUTRON
LUTRON
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
1 2 3 4 5 6 7 8 9 10
To wall controls
To wall controls
To wall controls
LZC1 Connections
Small Panel Connections
Standard Panel Connections
Note:
+24 V signal is made only to
the first LZC if wall controls
are wired to multiple LZCs.
Do not c24 V
connections together on
multiple LZCs. Instead, CIR
COM must be connected
together.
LZC LINK
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer
to the Lighting Zone
Controller Installer's Guide
(p/n 031-268).
Para la instalación, consulte
la Guía del Instalador de
Controlador de zona de luz
(p/n 031-268).
Pour installation, référer au
guide Contrôleur de zone
d‘Éclairage de l'installateur
(p/n 031-268).
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
www.lutron.com
Mexico
Coopersburg, PA 18036 USA
DMW-LZC1
ADDR
+24 V
PS SIG
PS COM
WC COM
WC SIG
+24 V
CIR COM
+15 V
OCC SIG
OCC COM
MUX
MUX
LNK COM
EMERG
SHLD
1-888-235-2910
1
2
3
4
5678
ON
®
100-277 V 50/60 Hz
16 A Max.
LISTED
Energy Management
Equipment 5C81
R
®