Appendix: Emergency Mode
(continued)
Wiring Method Two (continued)
Switch S1: Entire system will go into emergency mode when switch S1 is open.
Switch S2: Router Panel 1 or
GRAFIK
7000P processor panel 1 will go into Emergency mode when switch S2 is
open. Router Panel 2 or
GRAFIK
7000P processor panel 2 is unaffected by switch S2.
4 3 2 1
4 3 2 1
NTOMX-62J
NTOMX-45J
(used only if UI link
is connected
through RS485)
Digital microWATT
TM
System
GRAFIK
TM
7000 System
Digital microWATT
TM
System
GRAFIK
TM
7000 System
GUI
Link IN
GUI
Link OUT
No Connection
COM
COM
+V
+V
G+V
G+V
GCOM
GCOM
NC
GSHLD
GMUX
GMUX
GEMRG
GCOM
GSHLD
GMUX
GMUX
GEMRG
GCOM
+V
Common
SENSE
+33 V IP
SENSE
COM
COM
Switch S2
(normally
closed)
Switch S2
(normally
closed)
Switch S2
(normally
closed)
To SENSE on PP link of other processors
To COM on IP link* of other processors
To next
router
panel
Common
Emergency
MUX
To
NTOMX-62J
or previous
router panel
MUX
This page applies to:
LZC1
Small
Panel
Std.
Panel
R
Installation Guide for Lighting Zone Controllers 33
To COM on GUI link
To +V of first router panel
To MUX on GUI link
To MUX on GUI link
To COM on UI link
To MUX on UI link
To MUX on UI link
To COM on IP link*
(tie together all processors)
To EMERG on GUI link
To +33V IP on IP link* of first processor
To SENSE on PP link of all processors
Switch S1
(normally
closed)
{
}
IP Link*
PP Link
IP Link*
PP Link
*To enable interprocessor communication, either the IP
link’s MUX and MUX connections must be wired
together, or the Ethernet communication option must
be used. See the
GRAFIK Systems Centralized
Lighting Control System Installation and Maintenance
Guide
for details.
Switch S1
(normally
closed)