Appendix: Voltage Map
Fixture Voltage Map
Voltage
(use True RMS Voltmeter)
Without lamp
With lamp
Low end: 0.70 x line voltage
High end: 0.98 x line voltage
Line V/- 10%
4 to 8 V
3 to 5 V
4 to 8 V
3 to 5 V
4 to 8 V
3 to 5 V
4 to 8 V
3 to 5 V
Danger!
Readings must be done while the circuit
is energized. Apply the voltage only to the meter.
Danger!
Do not measure from one colored lamp
wire to another colored lamp wire (such as from
Red to Blue). This could exceed the voltage rating
of your meter.
True RMS
Voltmeter
Set the meter to AC Volts.
Use the highest scale for the
line voltage readings.
Use the 20 V
scale for the
filament voltage readings.
Note:
When measuring
voltages, keep the meter
body away from the lamps.
Where to Measure
Dimmed hot (orange)
to neutral (white)
Hot (black) to neutral
Blue to blue
Red to red
Yellow to yellow
Blue/white to
blue/white
Lighting Zone Controller Voltage Map
Common (black lead) of
meter to circuit common
Touch red lead to
other terminals
PELV (Class 2: USA)
wiring
Set the meter to DC Volts.
Use the appropriate scale for
the voltage readings.
3 -wire
dimming ballast
Hot (black)
Neutral (white)
Ground to fixture case
(green)
Dimmed hot (orange)
LZC LINK
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer
to the Lighting Zone
Controller Installer's Guide
(p/n 031-268).
Para la instalación, consulte
la Guía del Instalador de
Controlador de zona de luz
(p/n 031-268).
Pour installation, référer au
guide Contrôleur de zone
d‘Éclairage de l'installateur
(p/n 031-268).
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
www.lutron.com
Mexico
Coopersburg, PA 18036 USA
DMW-LZC1
ADDR
+24 V
PS SIG
PS COM
WC COM
WC SIG
+24 V
CIR COM
+15 V
OCC SIG
OCC COM
MUX
MUX
LNK COM
EMERG
SHLD
1-888-235-2910
12
3
4
5678
ON
®
100-277 V 50/60 Hz
16 A Max.
LISTED
Energy Management
Equipment 5C81
R
®
R
36
Installation Guide for Lighting Zone Controllers
Terminal
+24V
WC Sig
+15V
Occ Sig
EMERG
Occupant Sensor ON
21-26 V
14.1-16.2 V
<2 or >10 V
Occupant Sensor OFF 21-26 V
14.1-16.2 V
5-7 V
Wall control ON
21-26 V
1-26 V
14.1-16.2 V
Wall control OFF
21-26 V
<1 V
14.1-16.2 V
Emergency closed
21-26 V
14.1-16.2 V
0-7 V
Emergency open
21-26 V
14.1-16.2 V
21-26.6 V