R
Installation Guide for Lighting Zone Controllers 15
This page applies to:
Std.
Panel
Wiring
(continued)
From
distribution
panel
Black
Green
White
Orange
Black
Green
White
Lutron 3-wire
dimming ballast
Fixture ground
Switched load
Fixture ground
Output line voltage terminals
Standard Feed-Through Panel
Orange (DH1)
Red (SH1)
Black (H1)
Green/Yellow (G1)
White (N1)
White (N1)
Orange (DH2)
Red (SH2)
Black (H2)
Green/Yellow (G2)
White (N2)
White (N2)
Hot 1
Neutral 1
Hot 2
Neutral 2
Black
Green
White
Orange
Black
Green
Lutron 3-wire
dimming ballast
Fixture ground
Switched load
Fixture ground
Orange (DH1)
Red (SH1)
Black (H1)
Green/Yellow (G1)
White (N1)
White (N1)
Orange (DH2)
Red (SH2)
Black (H2)
Green/Yellow (G2)
White (N2)
White (N2)
Standard Panel with Main Lugs
Output line voltage terminals
Note:
For switchable loads (non-dimming),
make sure address switch 8 on the LZC is in
the ON position.
Note:
For switchable loads (non-dimming),
make sure address switch 8 on the LZC is in
the ON position.
Danger!
Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
Standard Panels: Load Wiring
Connect the input feed wires and the output load wires
to the lighting zone controller as indicated in the wiring
diagrams below. Colors indicated refer to the lighting
zone controller panel terminal block and ballast wire
colors.
(do not use)
(prewired)
(prewired)
(do not use)
(prewired)
(prewired)
Note:
Feed wiring is attached to main lugs at
bottom center of panel.
Bypass jumper (do not remove at this
time)
Bypass jumper (do not remove at this
time)
Note:
Maximum wire
length from
DMW-LZC1 to
last dimming
ballast is 750
feet (240 m).
Note:
Maximum wire
length from
DMW-LZC1 to
last dimming
ballast is 750
feet (240 m).
White