Installation and Maintenance Guide

L i g h t i n g   Z o n e   C o n t r o l l e r   a n d

L i g h t i n g   Z o n e   C o n t r o l l e r   P a n e l s

Models Available

Model #

# LZCs

Voltage

Enclosure

Feed Type

Breakers

DMW-LZC1

1

100-277 V

Self-enclosed

N/A

None

DMWP4-FT

4

100-277 V

Small panel

Feed-through

None

DMWP12-FT

12

100-277 V

Standard panel

Feed-through

None

DMWP18-FT

18

100-277 V

Standard panel

Feed-through

None

DMWP24-FT

24

100-277 V

Standard panel

Feed-through

None

DMW-LZC4

4

100-277 V

Small panel

Main lugs

None

DMWP12-1204ML-20

12

120 V

Standard panel

Main lugs

120 V

20 A

DMWP18-1204ML-20

18

120 V

Standard panel

Main lugs

120 V

20 A

DMWP12-2774ML-20

12

277 V

Standard panel

Main lugs

277 V

20 A

All models are rated at 50/60 Hz and up to 16 A per LZC.
DMWP4-FT is rated at 16 A total.

LZC1

Large
panel

Small
panel

LZC LINK

1

2

3

4

5

6

7

8

9

10

11 12 13 14 15

Lighting Zone Controller
Controlador de zona de luz

Contrôleur de zone d'Éclairage

For installation, refer 
to the Lighting Zone 
Controller Installer's Guide 
(p/n 031-268).

Para la instalación, consulte 
la Guía del Instalador de 
Controlador de zona de luz 
(p/n 031-268).

Pour installation, référer au 
guide Contrôleur de zone
d‘Éclairage de l'installateur 
(p/n 031-268).  

                      P/N 500-9066 Rev. F

USA, Canada

1-800-523-9466

www.lutron.com

Mexico

Coopersburg, PA 18036   USA

DMW-LZC1

ADDR

+24 V

PS SIG

PS COM

WC COM

WC SIG

+24 V

CIR COM

+15 V

OCC SIG

OCC COM

MUX

MUX

LNK COM

EMERG

SHLD

1-888-235-2910

1

23

4

5

6

7

8

ON

®

100-277 V       50/60 Hz
16 A Max.

LISTED
Energy Management
Equipment 5C81

R

®

Summary of Contents for DMW-LZC1

Page 1: ...anel Feed through None DMWP24 FT 24 100 277 V Standard panel Feed through None DMW LZC4 4 100 277 V Small panel Main lugs None DMWP12 1204ML 20 12 120 V Standard panel Main lugs 120 V 20 A DMWP18 1204...

Page 2: ...ZC can wire to a maximum of 1 daylight sensor One daylight sensor can control a maximum of 1 LZC Lighting load System Maximums Component Digital microWATT Router Panel GRAFIK 7000P Processor Panel on...

Page 3: ...120 V 1 2 HP 277 V Dims a maximum of 16 A of fluorescent light load using Lutron s 3 wire phase control dimming ballasts based on information from the Digital microWATT server or eLumen manager occup...

Page 4: ...range Black White Orange Black Neutral Green White Hot Black Orange Red Circuit breaker Line voltage wiring Load wiring Maximum length 750 ft 240 m Ground Cap off orange wire for switched loads Router...

Page 5: ...nergy Management Equipment 5C81 Questions Call Lutron T echnical Support Center 1 800 523 9466 24 hrs 7 days or visit our web site at www lutron com POWER INDICA TOR On Caution unit has power Off Unit...

Page 6: ...imensions are in inches mm Knockouts are 7 8 inch 22 mm in diameter This page applies to Small Panel Mounting the Small Panel PELV Class 2 USA wiring Preferred feed wiring panel with main lugs only In...

Page 7: ...egs and dimmed legs to loads 6 0 152 2 5 635 22 0 560 2 5 63 5 2 5 63 5 63 0 1600 52 4 1330 18 5 470 0 31 8 diameter 0 63 16 diameter 4 keyholes for surface mounting Knockouts for DMWP18 use only Punc...

Page 8: ...ient temperature 32 F 104 F 0 C 40 C Relative humidity 90 non condensing Mount panel where audible noise is acceptable internal relays click Mount panel within 7 of vertical Lutron recommends 1 4 in 6...

Page 9: ...m circuit breaker for your installation Testing the Circuit in Bypass Turn the input power ON after assuring that it is safe to do so Lights should go to full ON while in bypass If lights do not go to...

Page 10: ...0 60 Hz 16 A Max Green White Black Green ground White neutral Red switched hot Orange dimmed hot White Black Orange White Black Orange Colors indicated refer to the lighting zone controller and ballas...

Page 11: ...s 2 USA wiring only PELV Class 2 USA wiring only Small Panel with Main Lugs Small Feed Through Panel Notes Small Panel with Main Lugs Feed wiring mains voltage wiring 10 14 AWG 6 0 2 5 mm2 Small panel...

Page 12: ...Through Panel Notes Standard Panel with Main Lugs Feed wiring mains voltage wiring main input lug rating 1 4 AWG thru 250 MCM 25 120 mm2 per lug Cu Al only Torque to 250 in lb 30 N m Standard panels w...

Page 13: ...terminal blocks located on the right hand side of the panel There are up to 24 sets of terminal blocks each containing an orange red black green yellow and two white terminal blocks Each set of termi...

Page 14: ...n the ON position Input feed and output line voltage terminals Black Green White Orange Black Green Lutron 3 wire dimming ballast Fixture ground Switched load Fixture ground Orange DH1 Red SH1 Black H...

Page 15: ...erminals Note For switchable loads non dimming make sure address switch 8 on the LZC is in the ON position Note For switchable loads non dimming make sure address switch 8 on the LZC is in the ON posi...

Page 16: ...energize the breaker should not trip and total load current must be within the circuit breaker s limit and less than or equal to 16 A In a main lug panel circuit breaker 1 powers Circuit 1 s LZC and...

Page 17: ...r possible future use Removal is shown at right C Turn circuit breakers ON Note Re use the bypass jumpers whenever work is being done on a load Damage caused by short circuits and miswiring is not cov...

Page 18: ...ess switches typical ON 24 V PS Signal PS Common Circuit Common WC Common WC Signal 24 V 15 V OCC Signal OCC Common 1 2 3 4 5 6 7 8 9 10 Standard Panel Address switches typical Notes Address each ligh...

Page 19: ...4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8...

Page 20: ...G Shield MUX MUX Link Com EMERG Shield Lutron GRX CBL 46L series cable or equivalent MUX white MUX purple Link common black Emergency red Shield bare 22 AWG 0 64 mm2 22 AWG 0 64 mm2 12 AWG 2 5 mm2 12...

Page 21: ...icroWATT Hardware Installer s Guide p n 031 268 Para la instalaci n consulte la Gu a del Instalador de Digital microWATT Hardware p n 031 268 Pour installation r f rer au guide pour quincaillerie Digi...

Page 22: ...l microWATT Hardware Installer s Guide p n 031 268 Para la instalaci n consulte la Gu a del Instalador de Digital microWATT Hardware p n 031 268 Pour installation r f rer au guide pour quincaillerie D...

Page 23: ...g faceplates are required Testing The wall controls will not dim the lights at this time The lighting zone controllers will be in burn in mode for 100 hours to season the lamps upon initially being po...

Page 24: ...ications To occupant sensor LZC1 Connections Small Panel Connections Standard Panel Connections Wire to only one To additional LZCs maximum of 2 Wiring Occupant Sensors Turn power OFF to the LZC or LZ...

Page 25: ...n refer to the Digital microWATT Hardware Installer s Guide p n 031 268 Para la instalaci n consulte la Gu a del Instalador de Digital microWATT Hardware p n 031 268 Pour installation r f rer au guide...

Page 26: ...t the LED on the Occupant Sensor turns ON when motion is detected In addition the lights should turn ON when motion is detected the LED is lit and turn off approximately 30 seconds later provided the...

Page 27: ...ere is a wiring problem or a short in the circuit this will prevent damage to the lighting zone controller and or load interface Make the appropriate wire connections for your load type using the abov...

Page 28: ...taller s Gu ide p n 031 2 68 Para la ins talaci n consulte la Gu a del Ins talador de Co ntrola dor de zona de luz p n 031 2 68 Po ur ins tallation r f r er au guide Co ntr leu r de zone d clairag e...

Page 29: ...round Neutral LZC LINK 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Lighting Zone Controller Controlador de zona de luz Contr leur de zone d clairage For installation refer to the Lighting Zone Controller Inst...

Page 30: ...controller panels or the entire system depending on where the contact closure is placed Setting the Emergency Light Level The emergency light level is configured in the Digital microWATT or eLumen so...

Page 31: ...age de l installateur p n 031 268 P N 500 9066 Rev F USA Canada 1 800 523 9466 www lutron com Mexico Coopersburg PA 18036 USA DMW LZC1 ADDR 24 V PS SIG PS COM WC COM WC SIG 24 V CIR COM 15 V OCC SIG O...

Page 32: ...lutron com Mexico Coopersburg PA 18036 USA DMW LZC1 ADDR 24 V PS SIG PS COM WC COM WC SIG 24 V CIR COM 15 V OCC SIG OCC COM MUX MUX LNK COM EMERG SHLD 1 888 235 2910 1 2 3 4 5 6 7 8 ON 100 277 V 50 6...

Page 33: ...witch S2 normally closed To SENSE on PP link of other processors To COM on IP link of other processors To next router panel Common Emergency MUX To NTOMX 62J or previous router panel MUX This page app...

Page 34: ...COM WC SIGNAL 24V 15V OCC SIG OCC COM 24V PS Signal PS COM CIR COM WC COM WC SIGNAL 24V 15V OCC SIG OCC COM GND GND Switch S4 normally closed Emergency Shield MUX Link common MUX To panel or previous...

Page 35: ...rs at full intensity for the cleaners to do their job Without the 100 hours at full intensity the impurities may cause the lamp to fail within a week or failure may take months depending on usage and...

Page 36: ...Set the meter to DC Volts Use the appropriate scale for the voltage readings 3 wire dimming ballast Hot black Neutral white Ground to fixture case green Dimmed hot orange LZC LINK 1 2 3 4 5 6 7 8 9 1...

Page 37: ...em miswired Wrong lamp type for the ballast installed The Wall Control is at Low End The Occupant Sensor does not sense motion and the Lighting Zone Controller is set to go to Low End when the room is...

Page 38: ...llast installed Lamps are too old Black lamp ends or premature lamp failure Check that the fixture is properly grounded and that a ground plane is 1 2 in 1 4 in 13 mm 6 mm away from the lamp s entire...