4 - 14 Installation and Setup
Issue 6 August 1998
Alarm Outputs: The alarm outputs (BD, HV, ACF, LV,
PMNA, PMNV, PMNE, PMJA, PMJV, PMJE, MNF, and MJF)
are clean transfer contacts and are described functionally in
Section 2. Most office alarm systems are designed for EITHER
closure-on-alarm or open-on-alarm, requiring two wires from
each controller alarm that is used.
Alarm Inputs: The three alarm inputs (RMJ, RMN, and OS) are
compatible with battery voltage on alarm signals,
current-limited by resistors. These alarm inputs are general
purpose. They can be used to detect alarm conditions from any
auxiliary plant equipment, such as ringer, converter, inverter,
etc. The subsystems generating those alarms must be powered
off the same battery and ground system as the controller (i.e., the
dc distribution bus bars). A typical application is shown
schematically in Figure 4-5. Note that the resistor value for OS
is 1000 ohms and the values for RMN and RMJ are 4,640 ohms.
TB103-11
PMNVR
Power Minor Visual, return
TB103-12
PMNVO
Power Minor Visual, alarm
causes open
TB104-1 PMJAC
Power Major Audible, alarm
causes closure
TB104-2
PMJAR
Power Major Audible, return
TB104-3 PMJAO
Power Major Audible, alarm
causes open
TB104-4 PMJEC
Power Major External, alarm
causes closure
TB104-5
PMJER
Power Major External, return
TB104-6 PMJEO
Power Major External, alarm
causes open
TB104-7 PMJVC
Power Major Visual, alarm
causes closure
TB104-8
PMJVR
Power Major Visual, return
TB104-9 PMJVO
Power Major Visual, alarm
causes open
TB104-10
MJFEC
Fuse Alarm Major, External,
alarm causes closure
TB104-11 MJFER
Fuse Alarm Major, External,
return
TB104-12 MJFEO
Fuse Alarm Major, External,
alarm causes open
Table 4-G: Terminal Block Pin Assignments
for the 113A2 Control Unit
Pin No.
Designation
Definition