Lucent Technologies Lineage
®
2000 ECS-6 Controller J85501D-1
2 - 18 Product Description
Issue 6 August 1998
Plant Shunt
Compatibility
50 millivolts at 50, 100, 200, 300, 400, or
800 amperes
100 millivolts at 100, 200, 400, 600, or
800 amperes
Alarm Contact Rating
60 volts dc, 1.0 ampere, Form C
Temperature
32 to 122° F
(0 to 50° C)
Altitude
-200 to 13,000 feet (-61 to 3962 meters)
For altitudes of 5000 to 13,000 feet,
derate maximum temperature by 3.8
degrees Fahrenheit per 1000 feet above
5000 feet.
For altitudes of 1524 to 3962 meters,
derate maximum temperature by 0.656
degrees Celsius per 100 meters above
1524 meters.
Humidity
10% to 95% noncondensing
Electrostatic Discharge IEC 801-2 Level 5 (15kV) at 40% relative
humidity
Radiated and
Conducted Emissions
FCC Level A
Electromagnetic
Immunity
10 V/m over the range of 20 to 2000 MHz
LVD/R Voltage
Settings
40.5V +/-0.5V
or 42.5 +/-0.5V for 48V plants
20.25V +/-0.25V
or 21.25V +/-0.25V for 24V plants
Table 2-A: ECS-6 Controller Electrical Specifications