Lucent Technologies Lineage
®
2000 ECS-6 Controller J85501D-1
Issue 6 August 1998
Operation 6 - 3
11.
MNF indicator
Yellow LED, when lit,
indicates that a non-critical
overcurrent protector has
operated. Such protectors
include some controller fuses
and may also include battery
disconnect circuit breakers.
This is a MINOR alarm
condition.
12.
NORM indicator
Green LED is lit whenever
there are no alarms present,
to indicate normal operation.
The only other LED that may
be lit when the NORM LED
is lit is the EQ indicator.
13.
V+ and V- jacks
Test jacks are available for
monitoring the plant charge
bus voltage with an external
meter.
14.
Local terminal port
Opening in the front panel
reserved for the local
terminal port on the CP2
microprocessor board.
15.
ESD connector
Jack provided for
electrostatic discharge
grounding with a wrist strap.
The operator should be
grounded to this point before
opening the controller front
panel.
Table 6-A: Front Panel Switches and Indicators