Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-416
2 - 2 Product Description
Issue 2 August 1996
Circuit Breakers
Type: KS23616
Ratings: 3, 5, 10, 15, 20, 30, 45, 60 amperes
Type: KS22010, optional
Battery String Terminations
Type: Studded bus bar, accepts double-hole terminal
lugs, 1-inch centers
Size: Terminates 4/0 AWG conductors
Complement: 12 terminal lugs maximum, back to back
System Ground Termination
Type: studded bus bar, accepts double-hole terminal, 1
inch center
Size: Terminates 4/0 AWG conductor
Temperature
77°F (25°C) nominal
Altitude
-200 to 13000 feet (-61 to 3962 meters)
For altitudes of 5000 to 13,000 feet, derate maximum
temperature by 3.8°F per 1000 feet above 5000 feet.
For altitudes of 1524 to 3962 meters, derate maximum
temperature by 0.656°C per 100 feet above 1524
meters.
Framework
Type: 7 foot Network Bay Frame (standard 23 inch
relay rack)
Vertical mounting centers: 1.00 inches (25 mm)
Horizontal mounting centers: 22.32 inches (567 mm)
Dimensions
Height: 84 inches (2134 mm)
Width: 26 inches (660 mm)
Depth: 18.5 inches (470 mm)
Depth when equipped with VR batteries: 26 inches
(660 mm)
Weight
Initial bay, equipped with 12 rectifiers: 651 pounds
(296 kilograms)
Rectifier Shelf Assembly: 25 pounds (11.4 kilograms)
Rectifier: 25 pounds (11.4 kilograms)
Controller: 20 pounds (9.1 kilograms)
Earthquake
Initial bay: Zone 4, upper floors
Heat Dissipation
Initial Bay, full load, 12 rectifiers, controller: 6482
watts (22,098 BTU/hr) (See Note 1)
Rectifier, full load: 538 watts (1834 BTU/hr)
Controller, basic and options: 26 watts (89 BTU/hr)
Humidity rating
10% to 95% noncondensing
Audible noise
68 dBA (See Note 2)
Table 2-A: Lineage
®
2000 Battery Plant Specifications (Model H569-416)