Issue 5 November 2000
363-206-208
Stand-Alone (Local) Installation Tests for the DDM-2000 OC-12 Multiplexer
Lucent Technologies - Proprietary
See Notice on first page
Procedure
(1) Issue the command
test-alm:md=all
(TEST ALARM). At the repeat prompt,
enter the desired number of times for this test to be performed.
NOTE:
This test can be terminated at any time with the CANcel or DELete key.
NOTE:
This test will cycle through the following at 4-second intervals:
No alarm
CR alarm
MJ alarm
MN alarm
No alarm.
(2) Verify that both the audible and visual alarms are activated during this test.
(3) Repeat the office alarm test. This time, during each alarm cycle, immediately
press the ACO push-button and verify the audible alarms are silenced.