7-9
Operating command via FX, RX terminal 2
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
drv
[Drive mode]
2
0 ~ 4
1
I/O group
I17
[Multi-function input
terminal P1 define]
0
0 ~ 27
0
I18
[Multi-function input
terminal P2 define]
1
0 ~ 27
1
Set the
drv
to 2.
Set I17 and I18 to 0 and 1 to use P1 and P2 as FX and RX terminals.
FX: Operating command setting. Motor runs in forward direction when RX terminal (P2) is
OFF.
RX: Direction of motor rotation select. Motor runs in reverse direction when RX terminal
(P2) is ON.
Operating command via RS485 communication
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
drv
[Drive mode]
3
0 ~ 4
1
I/O group
I59
[Communication protocol
select]
-
0 ~ 1
0
I60
[Inverter number]
-
1 ~ 250
1
I61
[Baud rate]
-
0 ~ 4
3
Set the
drv
to 3.
Set I59, I60 and I61correctly.
Inverter operation is performed via RS485 communication.
Refer to Chapter. 13, RS485 communication.
FX
RX
Freq.
For Service Call
800-848-2504
For Service Call
800-848-2504
Summary of Contents for sv-ig5a
Page 10: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 14: ...1 4 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 28: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 47: ...4 19 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 48: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 74: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 80: ...6 6 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 184: ...v For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 185: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...