7-3
I6 ~ I10: Setting input range and corresponding frequency to 0 ~ +10V V1 input voltage
Ex) when minimum (+) input voltage is 2V with corresponding frequency 10Hz and Max
voltage is 8V with run freq.
Frequency setting via 0 ~ 10 [V] input or Terminal Potentiometer
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
0.00
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
3
0 ~ 9
0
I/O group
I 6
[Filter time constant for V1
input]
10
0 ~ 9999
10
I 7
[V1 input Min voltage]
-
0 ~ 10
0
V
I 8
[Frequency corresponding
to I 7]
-
0 ~ 400
0.00
Hz
I 9
[V1 input max voltage]
-
0 ~ 10
10
V
I10
[Frequency corresponding
to I 9]
-
0 ~ 400
60.00
Hz
Select 3 in Frq code of Drive group.
0-10V can be directly applied from an external controller or a potentiometer connected on
terminals VR, V1 and CM.
Wire the terminals as shown below and refer to I 6 ~ I 10.
VR
V1
CM
Wiring of potentiometer
V1
CM
0 ~ 10V input via external controller
Set freq.
V1 input
I 7
I 9
I 8
I 10
2V
8V
10Hz
50Hz
For Service Call
800-848-2504
For Service Call
800-848-2504
Summary of Contents for sv-ig5a
Page 10: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 14: ...1 4 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 28: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 47: ...4 19 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 48: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 74: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 80: ...6 6 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 184: ...v For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 185: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...