11-8
Note 1) The changed value in Common area affects the current setting but returns to the previous
setting when power is cycled or Inverter is reset. However, changing value is immediately reflected
in other parameter groups even in the case of Reset or Power On/Off.
Note 2) S/W version of Common area is displayed in Hexadecimal, while that of parameter area is
displayed in decimal.
Note 3) User can register up to Read address 8 ea/Write address 8 ea of discontinuous addresses
and read/write them n data(s) with one Read/Write command. Input/Output group I66 through I73
are registered in the common read addresses 0x0100 through 0x0107 and it can be read the
discontinuous n data(s) (less than 8 ea) with a read command. Input/Output group I74 through I81
are registered in the common write addresses 0x0108 through 0x010F and it can be written
discontinuous n data(s) (less than 8 ea) with a write command.
Address
Parameter
Scale
Unit
R/W
Allotment for Bits
0x000F
Trip information-A
-
-
R
B15 LVT
B14
IOLT
B13
POT
B12 FAN
B11
EEP
B10
EXT-B
B9
HW-Diag
B8
OLT
B7
ETH
B6
OHT
B5
GFT
B4
COL
B3
EST(BX)
B2
EXT-A
B1
OVT
B0
OCT
0x0010
Input terminal
status
-
-
R
B15, B14, B13, B12, B11, B10, B9, B8 : Reserved
B7
P8
B6
P7
B5
P6
B4
P5
B3
P4
B2
P3
B1
P2
B0
P1
0x0011
Output terminal
status
-
-
R
B7
3ABC
B4
MO
Others : Reserved
0x0012
V1
-
-
R
Value corresponding to 0 ~ + 10V input
0x0013
V2
-
-
R
Value corresponding to 0 ~ - 10V input when setting
Freq Mode to 2
0x0014
I1
-
-
R
Value corresponding to 0 ~ 20mA input
0x0015
RPM
-
-
R
See Function List
0x001A
Unit display
-
-
R
Not Used
0x001B
Pole number
-
-
R
Not Used
0x001C
Custom Version
-
-
R
Not Used
0x001D
Trip information-B
-
-
R
B5
NBR
B4
OC2
B3
REEP
B2
NTC
B1
FLTL
B0
COM
Others : Reserved
0x001E
PID Feedback
0.1
%
R/W
Writes feedback amount when feedback is set by
communication in PID drive.
0x001F
Output torque
0.01
kgf
m
R
Motor output torque display
0x0100
~
0x0107
Read address
register (Note3)
-
-
R
0x0100 : I66
0x0101 : I67
0x0102 : I68
0x0103 : I69
0x0104 : I70
0x0105 : I71
0x0106 : I72
0x0107 : I73
0x0108
~
0x010F
Write address
register (Note3)
-
-
W
0x0108 : I74
0x0109 : I75
0x010A : I76
0x010B : I77
0x010C : I78
0x010D : I79
0x010E : I80
0x010F : I81
For Service Call
800-848-2504
For Service Call
800-848-2504
Summary of Contents for sv-ig5a
Page 10: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 14: ...1 4 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 28: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 47: ...4 19 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 48: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 74: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 80: ...6 6 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 184: ...v For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 185: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...