10-2
10.2 Overload Warning and trip
Overload warning
Group
Code
Parameter
Set
Range
Initial
Unit
Function
group 1
F54
[Overload warning level]
-
30 ~ 150
150
%
F55
[Overload warning time]
-
0 ~ 30
10
Sec
I/O
group
I54
[Multi-function
output
terminal select]
5
0 ~ 19
12
I55
[Multi-function relay select]
5
17
Select one output terminal for this function between MO and 3ABC.
If selecting MO as output terminal, set I54 to 5 {Overload: OL}
F54: Set the value as a percent of motor rated current.
Current [%]
F51
F52
60
ETH trip time [sec]
Current
Multi-function
output
F54
t : Overload
warning time
t
t
For Service Call
800-848-2504
For Service Call
800-848-2504