8.17 Over voltage trip prevention deceleration and Power Braking
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 1
F 4
Select stop method
3
0 ~ 3
0
F 59
BIT 0: stall prevention
under Accel
BIT 1: stall prevention
under constant speed
BIT 2: stall prevention
under Decel
-
0 ~ 7
0
F 61
Select voltage limit under
Decel
-
0 ~ 1
0
To prevent overvoltage trip when reducing speed, set BIT2 of F59 to 1 and set 3 of F4 for
Power Braking.
Overvoltage trip prevention when reducing speed: a function preventing overvoltage trip when
reducing speed or at stop by using the regeneration braking power.
Power Braking : Adjusting the deceleration slope or ac
celerate again, when inverter‟s DC
voltage rises above a certain level by the electric motor‟s regeneration energy. It can be used
when short deceleration time without braking resistance is needed. However, be aware that the
deceleration time can get longe
r than the set one and when it‟s used at a load that frequently
decelerates, be cautious of damage caused by the motor‟s over heating.
Caution
Stall prevention and Power Braking only operate when decelerating, and Power
Braking has the precedence. That is, when BIT2 of F59 and Power Braking of F4 are
both set, Power Braking operates.
F61(selecting voltage restriction when decelerating) is visible when BIT2 of F59 is
set.
Overvoltage trip may occur, if the deceleration time is too short or the inertia too big.
8.18 External brake control
Group
Code
Name
Set nr.
Limit
Default Unit
Function
Group 2
H 40
Controlling method select
0
0~3
0
In/Output
Group
I 82
Brake open current
-
0~180.0 50.0
%
I 83
Brake open delay time
-
0~10.00 1.00
Sec.
I 84
Brake open CW Freq.
-
0~400
1.00
Hz
I 85
Brake open CCW Freq.
-
0~400
1.00
Hz
I 86
Brake close delay time
-
0~10.00 1.00
Sec.
I 87
Brake close Freq.
-
0~400
2.00
Hz
I 54
Multi-function output
terminal select
19
0~ 19
12
I 55
Multi-function relay select
19
0~ 19
17
I82~87 is visible only when I 54 or I 55 is set to 19.
For Service Call
800-848-2504
For Service Call
800-848-2504
Summary of Contents for sv-ig5a
Page 10: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 14: ...1 4 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 28: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 47: ...4 19 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 48: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 74: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 80: ...6 6 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 184: ...v For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Page 185: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...