Chapter 2. Functions
2-3
2.2
Memory configuration map
2.2.1
K10S1
Bit Data Area
Word Data Area
User Program Area
I/O relay
(32 points)
“P”
Auxiliary relay
(256 points)
“M”
Keep relay
(128 points)
“K”
Special relay
(256 points)
“F”
Link relay
(128 points)
“L”
P00
P01
M00
M15
K00
K07
F00
F15
L00
L07
Data Register
(64 words)
“D”
D000
D063
Timer Setting Value
(48 words)
T000
T047
T000
Timer Elapsed Value
(48 words)
Counter Setting Value
(16 words)
Counter Elapsed Value
(16 words)
T047
C000
C015
C000
C015
Parameter setting area
Word
User Program
Area
(800 steps)
Timer relay (100ms)
(32 points)
“T”
Timer relay (10ms)
(16 points)
“T”
Counter relay
(16 points)
“C”
T000
T031
T032
T047
C000
C015
Step Controller
(16 x 100 steps)
S00.00~S15.99
“S”
S00
S15
0 ~ F
0000 ~ FFFF
Retentive area
P area
None
T area
T024 ~ T031 (10msec)
K area
K000 ~ K07F
T044 ~ T047 (100msec)
L area
L00 ~ L07F
C area
C012 ~ C015
D area
D048 ~ D063
S area
S12.00 ~ S15.99