Chapter 2. Functions
2-1
2 Functions
2.1
Performance Specifications
2.1.1
K10S1 / K10S / K30S / K60S
Items
K10S1
K10S
K30S
K60S
Program control method
Cyclic execution of stored program
I/O control method
Indirect (Refresh) method
Basic
30
Numbers of
Instructions
Application
226
Processing speed
3.2 ~ 7.6
㎲/step
1.2
㎲/step
Program capacity
800 steps
2,048 steps
P (I/O relay)
P0000 ~ P001F
(32 points)
P0000 ~ P005F (96 points)
M (Auxiliary relay)
M0000 ~ M015F
(256 points)
M0000 ~ M031F (512 points)
K (Keep relay)
K0000 ~ K007F
(128 points)
K0000 ~ K015F (256 points)
L (Link relay)
L0000 ~ L007F
(128 points)
L0000 ~ L015F (256 points)
F (Special relay)
F0000 ~ F015F
(256 points)
F0000 ~ K015F (256 points)
100ms
T000 ~ T031
(32 points)
T000 ~ T095 (96 points)
T (Timer relay)
10ms
T032 ~ T047
(16 points )
T096 ~ T127 (32 points)
C (Counter relay)
C000 ~ C015
(16 points)
C000 ~ C127 (128 points)
S (Step controller)
S00.00 ~ S15.99
(16
×
100 steps)
S00.00~ S31.99 (32
×
100 steps)
D (Data register)
D0000 ~ D0063
(64 words)
D0000 ~ D0255 (256 words)
The range of integer
16 bit :
−
32768 ~ 32767
32 bit :
−
2147483648 ~ 2147483647
Timer types
On-delay, Off-delay, Accumulation, Monostable, Retriggerable (5 types)
Counter types
Up, Down, Up -down, Ring counter (4 types)
Programming language
Mnemonic, Ladder diagram
Special functions
Real time clock, High speed counter, RS-485 communication