Appendix
A-6
A.2.2
K200S / K300S / K1000S
1) F relay
Contact
Keyword
Function
Description
F0000
RUN mode
Turns on when the CPU in the RUN mode.
F0001
Program mode
Turns on when the CPU in the Program mode
F0002
Pause mode
Turns on when the CPU in the Pause mode
F0003
Debug mode
Turns on when the CPU in the Debug mode
F0006
Remote mode
Turns on when the CPU in the Remote mode
F0007
User memory
installation
Turns on when a user memory is installed.
F0008 and
F0009
Unused
F000A
User memory
operation
Turns on when a user memory is being
operated
F000B to F000E
Unused
F000F
p_STOP
Execution of the
STOP instruction
Turns on when the STOP instruction is being
operated.
F0010
p _ON
Always On
Always On
F0011
p_OFF
Always Off
Always Off
F0012
p_1ON
1 Scan On
1 Scan On
F0013
p_1OFF
1 Scan Off
1 Scan Off
F0014
p_STOG
Scan toggle
Scan toggle
F0015 to F001F
Unused
F0020
1 s tep run
Turns on when the 1 step run is operated in
the Debug mode.
F0021
Breakpoint run
Turns on when the breakpoint run is operated
in the Debug mode.
F0022
Scan run
Turns on when the scan run is operated in the
Debug mode.
F0023
Coincident junction
value run
Turns on when the coincident junction run is
operated in the Debug mode.
F0024
Coincident word
value run
Turns on when the coincident word run is
operated in the Debug mode.
F0025 to F002F
Unused
F0030
s_HEAVY_ER
Fatal error
Turns on when a fatal error has occurred.
F0031
s_LIGHT_ER
Ordinary error
Turns on when an ordinary error has occurred.
F0032
s_WD_ER
WDT Error
Turns on when a watch dog timer error has
occurred.
F0033
s_IO_TYER
I/O combination
error
Turns on when an I/O error has occurred.
(When one or more bit(s) of F0040 to F005F
turns on)
F0034
s_BAT_ER
Battery voltage
error
Turns on when the battery voltage has fallen
below the defined value.
F0035
s_FUSE_ER
Fuse error
Turns on when a fuse of output modules has
been disconnected.
F0036 to F0038
Unused
F0039
s_D_BCK_OK
Normal backup
operation
Turns on when the data backup is normal.
F003A
s_RTC_ER
RTC data error
Turns on when the RTC data setting error has
occurred.
F003B
During program
edit
Turns on during program edit while running
the program.
F003C
Program edit error
Turns on when a program edit error has
occurred while running the program.
F003D to F003F