Chapter 5. Application instructions
5-122
5.17.5 STATUS
STATUS
(Read the link information of
FUEA module of remote station)
FUN(247) STATUS
Applicable
CPU
K200S
K300S
K1000S
Available Device
Flag
Instructions
M
P
K
L
F
T
C
S
D
#D Integer
Steps
Error
(F110)
Zero
(F111)
Carry
(F112)
O
O O O O O O O
O O
O O O O*
O O
O O
STATUS
O O O O*
O O
O O
9
O
* Available only when do not use computer link module or data link module
1) Functions
-
Read the link information (10 words) from the remote station of which station number is ‘St’ through
the FUEA module mounted at the slot number ‘sl’, and stores the information data to the block
begin with the device specified as [ D ]. The link status is stored into the device [ SS ].
-
Execution conditions
2) Program example
- Program that reads the information of remote station (station number is stored at D0000) through the
FUEA module of slot 07, and stores the data from D1234. The link status is stored into K015 word.
D
sl
St
SS
STATUS
St
D
sl
SS
Operand setting
Slot number of FUEA module is
mounted & Type of special
function module to be read
Station number of remote station
to be read data & Slot number of
special function module
Start address of remote station at
which data to be written
sl
D
SS
St
Device at which the link status is
stored
Input condition
RPUT
Executed only once
Executed only once
STATUS h0007 D0000 D1234 K015