LSI LASTEM M-Log – User’s manual
42
Included
: alarm in case the measure value if greater than the minimum threshold value and
at the same time lesser than the maximum threshold value; return to no alarm condition
when the measure value is lesser than the minimum threshold value or greater than the
maximum threshold; hysteresis is used like shown in the following example: threshold
values=2.0 and 4.0 and hysteresis=0.2 (alarm in shaded areas):
Excluded
: alarm in case the measure value if lesser than the minimum threshold or greater
than the maximum threshold; return to no alarm condition when the measure value is greater
than the minimum threshold and at the same time lesser than the maximum threshold;
hysteresis is used like shown in the following example: threshold values=2.0 and 4.0 and
hysteresis=0.2 (alarm in shaded areas):