7. Function list
7-1
SV-iC5
7. Function list
Drive Group
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
0.0
[Frequency
command]
0/400
[Hz]
This parameter sets the frequency that the
inverter is commanded to output.
During Stop: Frequency Command
During Run: Output Frequency
During Multi-step operation: Multi-step
frequency 0.
It cannot be set greater than F21- [Max
frequency].
0.0
O
9-1
ACC
[Accel time]
0/6000
[sec]
During Multi-Accel/Decel operation, this
parameter serves as Accel/Decel time 0.
5.0
O
9-10
dEC
[Decel time]
10.0
O
9-10
Drv
[Drive mode]
(Run/Stop
mode)
0/3
0
Run/Stop via Run/Stop key on the keypad
1
X
9-7
1
Run/Stop
via control
terminal
FX : Motor forward run
RX : Motor reverse run
9-7
2
FX : Run/Stop enable
RX : Reverse rotation select
3
Operation via Communication Option
Frq
[Frequency
mode]
0/8
0
Digital
Setting via Keypad 1
0
X
9-1
1
Setting via Keypad 2
9-1
2
Analog
Setting via potentiometer on
the keypad(V0)
9-2
3
Setting via V1 terminal
9-3
4
Setting via I terminal
9-3
5
Setting via potentiometer on
the I terminal
9-4
6
Setting via V1 + I terminal
9-4
7
Setting via potentiometer on
the V1 terminal
9-5
8
Modbus-RTU Communication
St1
[Multi-Step
frequency 1]
0/400
[Hz]
This parameter sets Multi-Step frequency 1
during Multi-step operation.
10.0
O
9-6
St2
[Multi-Step
frequency 2]
This parameter sets Multi-Step frequency 2
during Multi-step operation.
20.0
O
9-6
St3
[Multi-Step
frequency 3]
This parameter sets Multi-Step frequency 3
during Multi-step operation.
30.0
O
9-6
Summary of Contents for SV iC5 Series
Page 8: ...Table of Contents viii SV iC5...
Page 22: ...3 Wiring 3 6 SV iC5 Notes...
Page 38: ...5 Programming keypad 5 14 SV iC5 Notes...
Page 42: ...6 Basic operation 6 4 SV iC5 Notes...
Page 64: ......
Page 68: ......
Page 108: ...10 Advanced functions 10 20 SV iC5 Notes...
Page 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes...
Page 136: ......
Page 142: ......
Page 143: ......